UV Dose Calculation and Germicidal Effect

Diagram of UV dose calculation showing intensity, exposure time and germicidal effect relationships
UV dose and germicidal effect explained

UV dose is the core indicator for measuring the effectiveness of ultraviolet disinfection, and dose calculation is the key to designing and selecting a UV sterilizer. This article explains in detail how UV dose is calculated and how it relates to germicidal performance.

1. Basic concepts of UV dose

1.1 Definition

UV dose is the total energy received by a microorganism from UV irradiation; it equals UV intensity multiplied by exposure time.

Formula: D = I × t

  • D: dose (mJ/cm²)
  • I: UV intensity (mW/cm²)
  • t: exposure time (s)
  • Unit conversion: 1 mW/cm² × 1 s = 1 mJ/cm²

1.2 Importance of dose

  • Dose determines germicidal effectiveness
  • Insufficient dose results in incomplete disinfection
  • A sufficient dose can inactivate nearly all microorganisms
  • Dose is the core design parameter of a UV sterilizer

2. UV intensity distribution

2.1 Point-source intensity decay

UV intensity decays with the square of distance: I = I₀ / (4πr²)

  • I₀: output power of the light source
  • r: distance from the light source
  • The greater the distance, the lower the intensity

2.2 Intensity distribution in the chamber

  • At the lamp centre: highest intensity
  • Near the tube wall: lower intensity
  • Multi-lamp designs: more uniform intensity
  • Actual intensity distribution is non-uniform, so the minimum-dose point must be calculated

2.3 Factors affecting intensity

  • Lamp power: higher power gives higher intensity
  • Number of lamps: more lamps give higher and more uniform intensity
  • Chamber diameter: a larger diameter lowers intensity at the tube wall
  • Quartz sleeve transmittance: higher transmittance gives higher intensity
  • Water quality: high turbidity weakens UV penetration and lowers intensity

3. Calculating exposure time

3.1 Theoretical calculation

t = V / Q

  • t: exposure time (s)
  • V: effective chamber volume (m³)
  • Q: flow rate (m³/s)

3.2 Real-world conditions

  • Flow velocity is not uniformly distributed
  • Flow is faster at the centre and slower near the tube wall
  • Some water may short-circuit (without receiving adequate irradiation)
  • Actual exposure time is shorter than the theoretical value
  • CFD (computational fluid dynamics) simulation is required

3.3 Effective exposure time

  • Actual exposure time after accounting for flow distribution
  • Generally 60 to 80 percent of the theoretical time
  • A safety margin must be reserved in design

4. Dose calculation methods

4.1 Simplified method

D = (P × η × τ × t) / V

  • P: total lamp power (W)
  • η: electrical-to-optical conversion efficiency (35 to 40 percent for low-pressure lamps)
  • τ: quartz sleeve transmittance (≥90 percent)
  • t: exposure time (s)
  • V: effective chamber volume (m³)
  • Dose (mJ/cm²) is obtained after unit conversion

4.2 Average dose method

D_avg = (P × η × τ) / Q × 1000

  • P: total lamp power (W)
  • η: electrical-to-optical conversion efficiency
  • τ: transmittance
  • Q: flow rate (m³/h)
  • 1000: unit conversion factor
  • Gives the average dose (mJ/cm²)

4.3 Biological dosimetry (most accurate)

  • Use an indicator organism (MS2 phage or Escherichia coli)
  • Measure the microbial concentration in the inlet and outlet water
  • Calculate the inactivation rate
  • Read the actual dose from the dose-inactivation curve
  • Performed by a third-party testing agency

4.4 CFD and radiation modelling method

  • Simulate flow distribution with computational fluid dynamics
  • Calculate the UV field with a radiation transfer model
  • Calculate the dose received by each water element
  • Obtain the dose distribution and the minimum dose
  • Used in the design of large equipment

5. Dose and germicidal effect

5.1 Microbial sensitivity to UV

Microorganism type Dose for 99.99% inactivation Sensitivity
Bacteria (Escherichia coli, Salmonella) 5 to 15 mJ/cm² High
Viruses (hepatitis virus, poliovirus) 10 to 30 mJ/cm² Medium-high
Bacterial spores (Bacillus anthracis) 30 to 60 mJ/cm² Medium
Protozoa (Cryptosporidium, Giardia) 40 to 100 mJ/cm² Low
Mould spores 30 to 60 mJ/cm² Medium

5.2 Dose-inactivation curve

  • As dose increases, the inactivation rate rises logarithmically
  • General rule: doubling the dose adds one log of inactivation (from 90% to 99%)
  • 40 mJ/cm² inactivates 99.99% of bacteria and viruses
  • 100 mJ/cm² inactivates nearly all microorganisms

5.3 Germicidal effect at different doses

Dose Inactivation rate Application
10 mJ/cm² 90% Preliminary disinfection of wastewater
20 mJ/cm² 99% Secondary effluent of wastewater
40 mJ/cm² 99.99% Drinking water (national standard)
60 mJ/cm² 99.999% Direct drinking water, high-quality supply
80 mJ/cm² 99.9999% Demanding direct drinking water, swimming pools
100 mJ/cm² >99.9999% Nearly all microorganisms

6. Factors affecting disinfection performance

6.1 Water quality factors

  • Turbidity: high turbidity means particles shield microorganisms from UV, reducing effectiveness
  • Colour: high colour absorbs UV
  • Iron: iron deposits on the sleeve, lowering transmittance
  • Suspended solids: particles can embed microorganisms and protect them

6.2 Equipment factors

  • Lamp power and number of lamps
  • Chamber design (flow distribution)
  • Quartz sleeve transmittance
  • Degree of lamp ageing

6.3 Operational factors

  • Flow rate: above the rated flow, dose drops
  • Lamp operating hours: power declines as lamps age
  • Sleeve cleanliness: scaling reduces transmittance

7. Dose verification

7.1 Design verification

  • Verify that the dose meets the standard using calculation methods
  • Provide a dose calculation report

7.2 Factory verification

  • UV intensity testing
  • Operating parameter testing

7.3 On-site verification

  • Water testing: total bacterial count and total coliforms in the outlet
  • Biological dosimetry testing (third party)
  • On-site UV intensity measurement

8. Longkang’s dose assurance

  1. Designed to national standards with a dose of ≥40 mJ/cm²
  2. A reserve margin of 20 to 50 percent is recommended
  3. A dose calculation report is provided
  4. Third-party biological dosimetry reports can be provided
  5. Optional online UV intensity monitoring
  6. Dose compliance is maintained even at the end of lamp life
  7. Support with on-site water quality testing