Hygienic Safety Evaluation of Drinking Water Disinfectants

Disinfection equipment used in drinking water hygienic safety evaluation
Hygiene requirements for drinking water disinfectants

This specification was developed under the Measures for the Sanitary Supervision and Administration of Drinking Water and the Measures for the Administration of Disinfection. It applies to the hygienic safety evaluation of disinfectants and disinfection equipment used for drinking water and sets out the hygiene requirements and test methods for such products. It covers products including sodium hypochlorite, chlorine dioxide, potassium permanganate and hydrogen peroxide.

1. Scope

The specification applies to the hygienic safety evaluation of disinfectants and disinfection equipment used for drinking water, and defines the hygiene requirements and test methods for these products. It is applicable to sodium hypochlorite, chlorine dioxide, potassium permanganate, hydrogen peroxide and similar products.

2. Definitions

The following definitions apply to this specification.

2.1 Disinfectant

A chemical treatment agent that kills microorganisms in drinking water.

2.2 Disinfection equipment

Equipment that generates a drinking water disinfectant or produces a disinfecting effect.

2.3 Disinfection by-product

A by-product generated during disinfection of drinking water after the use of a disinfectant or disinfection equipment.

2.4 New product

A disinfectant or disinfection equipment produced on the basis of a new principle or new active ingredient, and new formulations or new compound preparations of disinfectants.

3. Hygiene requirements

3.1 General

All disinfectants and disinfection equipment, when used as directed in the instructions and tested by the procedures listed in Table 1, shall achieve the purpose of drinking water disinfection in every test result, and all microbial indices shall comply with the current Hygienic Specifications for Drinking Water Quality.

3.2 Residues and by-products

The residues of disinfectant left in drinking water during disinfection and the levels of impurities introduced from raw materials and process steps shall not exceed the limits of the current Hygienic Specifications for Drinking Water Quality. The concentrations of disinfection by-products generated during disinfection shall not exceed the limits of that specification.

3.3 Unspecified harmful substances

Where a disinfectant, its raw materials or by-products, or water after use of disinfection equipment may contain harmful substances not specified in the current Hygienic Specifications for Drinking Water Quality, the limit for such a substance in drinking water may be judged by reference to relevant domestic and foreign standards, and the increase in that substance shall not exceed 10 percent of the relevant standard limit. If no relevant standard is available for reference, tests shall be carried out under the toxicological safety evaluation procedure to determine the maximum permissible concentration in drinking water; the permissible increase shall be 10 percent of that maximum concentration.

3.4 Hygiene requirements for disinfectants

When used as directed and calculated at the evaluation doses in Table 2, the increases in heavy-metal ions, inorganic substances and organic substances in treated drinking water shall not exceed 10 percent of the limits specified in the current Hygienic Specifications for Drinking Water Quality; total alpha and total beta radioactivity shall not increase. Test results obtained under Table 3 shall comply with the current Hygienic Specifications for Drinking Water Quality.

3.5 Hygiene requirements for disinfection equipment

When used as directed and calculated at the evaluation doses in Table 2, the increases in heavy-metal ions, inorganic substances and organic substances in treated drinking water shall not exceed 10 percent of the limits in the current Hygienic Specifications for Drinking Water Quality; total alpha and total beta radioactivity shall not increase. Soaking tests on the parts of the equipment that contact drinking water shall comply with the Hygienic Safety Evaluation Specifications for Drinking Water Distribution Equipment and Protective Materials.

4. Testing

4.1 Disinfectants

The overall performance test shall be carried out on the items specified in Table 3. Disinfection efficacy shall be tested on the items in Table 1; for drinking water source water in epidemic areas or under special conditions, the efficacy test shall follow section 2.1.4 of the Technical Standards for Disinfection (2002 Edition). Main raw materials shall be tested under the disinfectant items in section 3.4 of the Provisions of the Ministry of Health for the Inspection of Products Involving Drinking Water Hygiene and Safety (2001 Edition).

4.2 Disinfection equipment

The overall performance test shall be carried out on the items in Table 3, and disinfection efficacy on the items in Table 1; for source water in epidemic areas or under special conditions, the test shall follow section 2.1.4 of the Technical Standards for Disinfection (2002 Edition). Parts of the equipment that contact drinking water shall undergo the soaking test under section 3.3 of the Provisions of the Ministry of Health for the Inspection of Products Involving Drinking Water Hygiene and Safety (2001 Edition). The main chemical raw materials of the disinfectant generated by the equipment shall be tested under Appendix A and Table 3.

5. Test methods

5.1 Sampling and preparation

Sampling and preparation of chemical disinfectants for drinking water are described in Appendix A.

5.2 Physicochemical and microbial methods

Physicochemical and microbiological test methods shall follow the Inspection Specifications for Drinking Water (2001 Edition). Appendix B supplements that specification with test methods for antimony and chlorite, and serves as the first method for detecting those substances.

5.3 Toxicological evaluation

The specific steps of the toxicological safety evaluation procedure and test methods for chemical disinfectants used in drinking water shall follow Appendix B of the Safety Evaluation Specifications for Chemical Treatment Agents for Drinking Water (2001 Edition).

6. Test item tables

Table 1 lists the items tested for disinfection effect. Table 2 gives the evaluation doses for drinking water disinfectants. Table 3 lists the items in the overall performance test. In the tables, a check mark denotes an item that must be measured, and a triangle denotes an item to be measured if present.

Longkang provides disinfection equipment and selection support for drinking water applications. Contact Longkang for selection support.

UV disinfection, storage tank treatment, on-site hypochlorite (OSHG), chlorine dioxide and ozone systems for municipal, high-rise booster and industrial water.

Contact

Hotline +86 4008-780-280

Mobile / WhatsApp +86 130 1601 3265

R&D center, Guangzhou +86 20 28185170

Plant in Xianning, Hubei · R&D in Guangzhou, Guangdong