UV Disinfection System Design for Water Plants

Health authorities set stricter microbial and disinfection-by-product indicators in GB 5749—2006 (Standards for Drinking Water Quality). The number of microbial indicators rose from two to six, including the chlorine-resistant “two protozoa”: Giardia <1 per 10 L and Cryptosporidium <1 per 10 L. Safe disinfection must be ensured while the formation of disinfection by-products is effectively controlled. Because these microorganisms are chlorine-resistant and cannot be killed by chlorine disinfection, UV disinfection technology has become one of the important options for treatment in domestic water purification processes.
1. Main design parameters
The main design parameters of a UV disinfection system for a water treatment plant include UV transmittance (UVT), design flow, lamp aging and the fouling factor.
2. UV transmittance (UVT)
UVT is one of the important design parameters of a disinfection system. For low-pressure lamp systems, it is sufficient to measure UV transmittance at 254 nm. For medium-pressure lamp systems, UVT between 200 and 300 nm is also necessary, because the spectrum emitted by medium-pressure lamps includes this effective disinfection wavelength range. For a plant with stable UVT, monitoring for one to two months is sufficient. If source water quality changes with the seasons, a longer measurement period is needed (six to twelve months or more). A cumulative UVT frequency percentage curve is then plotted from the data. Because maximum flow and minimum UVT rarely occur at the same time, the value at P = 95% cumulative frequency is generally used as the design value when selecting UVT. The UVT setting has a major influence on the scale of the system: for one reactor model, raising UVT from 85% to 90% at the same 40 mJ/cm² dose can increase treatment capacity by 40%.
3. Design flow
The design flow of a UV disinfection system must include average, maximum and minimum flow. For a single filter, the effluent flow of that filter can be used; for the combined effluent of several filters, the treatment flow of all filters should be considered (excluding standby filters); for a system downstream of the clean water tank, the design flow may be selected according to the flow of the delivery pump station. US EPA regulations stipulate that UV disinfection reactors may not operate above the validated flow, so the number of reactors must be determined by the design maximum flow. In addition to meeting maximum-flow operation, at least one reactor must be kept as a standby. The design minimum flow is considered mainly so that some reactors can be shut down during operation to improve efficiency, save energy and reduce operating costs.
4. Lamp aging and fouling factor
UV lamps need quartz sleeves for protection, and fouling of the sleeves in water affects UV propagation. The main factors influencing sleeve fouling are lamp operating temperature and the chemical composition of the water. In general, a higher lamp operating temperature leads to faster fouling, and higher concentrations of calcium, iron, aluminium, manganese and carbonate ions in the water also accelerate fouling. Fouling also depends on the sleeve fouling factor and the cleaning system. Lamps age during service, so the aging factor over the lamp’s service life must be taken into account. The sleeve fouling factor and aging factor are determined through validation. According to a 2003 report by the National Water Research Institute (NWRI), the product of the fouling factor and the aging factor is generally between 0.4 and 0.9; this coefficient can be used to calculate whether the validated reactor dose is higher than the design dose.
5. System design and installation
In designing a plant UV disinfection system, the disinfection target should be set according to raw water quality and the treatment process, and the design effective dose and other key parameters of the UV reactor should be determined through validation. When selecting the installation position, a detailed hydraulic and cost analysis should be carried out based on actual plant conditions, and hydraulic conditions no less favourable than those during reactor validation should be provided.