Do UV Lamps Produce Ozone?

Do UV Lamps Produce Ozone? — Longcom technical note

No lamp contains ozone. Some lamps generate it as a side effect — and the deciding component is the quartz sleeve, not the arc tube.

Two wavelengths, two jobs

Low-pressure mercury lamps emit strongly at 253.7 nm, the germicidal line. They also emit at 185 nm. The 254 nm photons are absorbed by microbial DNA; the 185 nm photons are absorbed by oxygen and split it, producing ozone. Ozone is a powerful oxidant and a gas, which is why it can reach surfaces a straight UV beam cannot — a genuine advantage in cabinet, duct and air disinfection. In a closed water reactor it is usually unwanted.

How the three lamp classes are made

When quartz is refined, adding a controlled amount of titanium cuts off transmission below about 200 nm while leaving 253.7 nm essentially untouched. Vary the titanium content and you get three products from otherwise similar tubes:

  • Ozone-free. 185 nm suppressed. Standard for water reactors and most occupied-space applications.
  • Ozone-producing. A controlled 185 nm fraction for combined UV + ozone disinfection.
  • High-ozone. Deliberately high 185 nm output for dedicated ozone generation and odour treatment.

Early lamps only managed about 70% transmission because quartz purity was poor. Modern high-purity fused silica passes 90% or more at 253.7 nm — which is why sleeve material is a performance decision as well as a cost one.

Why it matters in a water system

For an in-line UV reactor, specify ozone-free lamps. Ozone in a pressurised chamber adds off-gas handling, materials compatibility and operator exposure concerns for no disinfection gain — the water is already in contact with the UV-C field. Where ozone is genuinely wanted, it is generated deliberately in an ozone generator with a contactor and an off-gas destructor, not as a lamp by-product.

If a supplier’s data sheet does not state which lamp class is fitted, ask. It is a one-line specification that changes the whole safety case.

Need a system sized for your water? Send us your flow rate, UV transmittance (UVT) and the target log reduction, and our engineers will specify the reactor and validated dose. Explore the product range or browse the Technical Library.

Condensed from our Chinese technical article. Read the full Chinese version.

UV disinfection, storage tank treatment, on-site hypochlorite (OSHG), chlorine dioxide and ozone systems for municipal, high-rise booster and industrial water.

Contact

Hotline +86 4008-780-280

Mobile / WhatsApp +86 130 1601 3265

R&D center, Guangzhou +86 20-2818 5170

Plant in Xianning, Hubei · R&D in Guangzhou, Guangdong