Four UV Faults You Can Fix on Site

Four UV Faults You Can Fix on Site — Longcom technical note

Four faults account for a large share of UV service calls. The first response is almost always the same: isolate power, close the inlet and outlet valves, and drain the chamber. Then work through the symptom.

One — water at the sleeve end

Split it by severity. A fast, heavy leak usually means a cracked quartz sleeve; replace it. A slow drip or seep is almost always a seal — tighten the gland evenly (over-torquing cracks quartz), or reseat the O-ring. Lubricate the ring with silicone grease on reassembly and pressure-test before restoring flow. For the wider diagnostic table, see the field checklist.

Two — scale on the quartz sleeve

Units with automatic wipers handle this themselves. Without one: stop flow, drain the chamber, withdraw the sleeve carefully and wipe it with alcohol on a clean cloth. On a multi-lamp bank this is a slow job, which is a decent argument for specifying online cleaning at purchase. Hard, iron- or manganese-rich water needs a set cleaning interval, not an ad hoc one.

Three — the lamp glows an odd colour

A dim green-yellow output usually means the ballast’s starting voltage does not match the lamp. Compare the ballast’s actual ratings with the lamp’s specification before ordering anything. A slow leak, wrong lamp wattage or an undersized transformer produce the same picture — see lamp diagnosis.

Four — the breaker trips

A trip is leakage or short-circuit. Check two places first: loose or displaced wiring inside the control cabinet, and water ingress at the lamp-to-socket connection. Both are common after a sleeve service. Do not keep resetting the breaker — find the moisture path.

One rule across all four

None of these is fixed by fitting a new lamp blindly. Log the symptom, the lamp hours and the intensity reading, and check whether the same fault recurs in the same module. A repeat failure is a design or installation problem — clearance, flow, pressure, water quality — not bad luck with consumables.

Need a system sized for your water? Send us your flow rate, UV transmittance (UVT) and the target log reduction, and our engineers will specify the reactor and validated dose. Explore the product range or browse the Technical Library.

Condensed from our Chinese technical article. Read the full Chinese version.

UV disinfection, storage tank treatment, on-site hypochlorite (OSHG), chlorine dioxide and ozone systems for municipal, high-rise booster and industrial water.

Contact

Hotline +86 4008-780-280

Mobile / WhatsApp +86 130 1601 3265

R&D center, Guangzhou +86 20-2818 5170

Plant in Xianning, Hubei · R&D in Guangzhou, Guangdong