Sodium Hypochlorite Generators
An on-site generator makes sodium hypochlorite from three inputs that are easy to buy and easy to store: salt, softened water and electricity. Saturated brine is diluted to about 3 percent, passed through an electrolytic cell with a divided membrane, and leaves as hypochlorite at roughly 8 grams of available chlorine per litre. The alternative — buying 12 percent bulk hypochlorite — means transporting a decaying oxidant, storing it in a bunded tank and watching its strength fall by a few percent a week in summer.
The case for generating on site is therefore strongest where consumption is steady, where delivery is difficult, and where the operator wants to avoid storing a concentrated oxidant. The case against is capital cost and the maintenance discipline that a brine system demands. Both sides deserve an honest number before a project commits.
The electrochemistry, in practical terms
At the anode, chloride is oxidised to chlorine; at the cathode, water is reduced to hydrogen and hydroxide. The two recombine to form hypochlorite. Two by-products follow from that chemistry and both shape the installation.
Hydrogen is produced at a fixed ratio: about 0.31 normal cubic metres per kilogram of chlorine equivalent. It leaves with the catholyte and must be vented outdoors, from the highest point of the storage tank, through a dedicated pipe with no low points and no common connection with any other vent. The generator room needs mechanical ventilation sized for at least twelve air changes per hour, a hydrogen detector at ceiling level, and an interlock that stops the cell on alarm. Hydrogen at 4 percent in air is explosive; the design must keep the room well below that under any single failure.
Chlorate and perchlorate form when the anolyte stays too long in the cell or when the pH drifts. Running at the specified brine concentration, cell temperature and flow is what keeps chlorate formation within the limits that drinking-water regulators set. A generator run at half flow to stretch capacity will meet a chlorine output figure and fail a chlorate test.
Consumption figures you can budget against
| Input | Per kg available chlorine | Note |
|---|---|---|
| Salt (NaCl) | 4.0 – 4.5 kg | Food grade, low calcium and magnesium |
| DC power | 4.5 – 5.5 kWh | Cell only; add 10 – 15 % for ancillaries |
| Softened water | 150 – 200 L | Hardness below 20 mg/L as CaCO3 |
| Hydrogen by-product | 0.31 Nm³ | Vent to outdoor atmosphere |
| Hypochlorite concentration | 6 – 9 g/L | Store below 30 °C, use within 7 – 10 days |
Multiply by local prices and the running cost is arithmetic rather than a claim. In most of Europe and China, salt and power together put the chemical cost of on-site hypochlorite close to bulk delivery, and the decision then turns on storage, transport and the value of not holding concentrated oxidant on site.
Sizing a station
Start from the chlorine demand, not from the water flow. Demand equals the dose in mg/L multiplied by the flow in m³/h, which gives grams per hour. For a secondary supply with a 0.3 mg/L residual target and 200 m³/h peak flow, that is 60 g/h at peak; the generator is then sized on daily production with a margin for the hours it is off, typically 1.5 to 2 times the peak hourly figure, and paired with a storage tank holding three to seven days of production.
| Model | Capacity | Salt per day | Power | Storage tank |
|---|---|---|---|---|
| LK-NaClO-100 | 100 g/h | 10 kg | 0.6 kW | 0.5 m³ |
| LK-NaClO-300 | 300 g/h | 30 kg | 1.6 kW | 1 m³ |
| LK-NaClO-500 | 500 g/h | 50 kg | 2.7 kW | 2 m³ |
| LK-NaClO-1000 | 1 kg/h | 100 kg | 5.2 kW | 3 m³ |
| LK-NaClO-3000 | 3 kg/h | 300 kg | 15 kW | 8 m³ |
| LK-NaClO-10000 | 10 kg/h | 1,000 kg | 50 kW | 25 m³ |
Why softened water is not optional
Calcium and magnesium in the feed precipitate on the cathode as carbonate scale. The scale raises cell voltage, then blocks the gap between the electrodes, then forces the operator to acid-wash the cell every few weeks instead of every few months. A softener ahead of the brine tank, with hardness below 20 mg/L as CaCO3, is the difference between a five-year electrode life and an eighteen-month one. Where softening is impossible, a scale-inhibiting dosing set is the fallback, and the cleaning interval should be halved in the maintenance plan.
Storage and decay
Hypochlorite at 8 g/L decays measurably. At 25 °C expect 1 to 2 percent loss per day; at 35 °C it can be 3 percent or more. Storage tanks should be HDPE or FRP, opaque, vented, and out of direct sun. Keep the tank sized for a week rather than a month: a large tank holds a weaker solution for longer and delivers less chlorine than the arithmetic suggests. Never store hypochlorite in a tank that previously held acid without a documented neutralisation and washout — the residue generates chlorine gas.
Installation checklist
House the generator in a room with a floor drain, a water supply for rinsing, and a bunded chemical area. Separate the salt storage from the cell; salt dust is corrosive to electronics and the brine tank is the heaviest item to move later. Mount the control cabinet outside the wet zone. Route the hydrogen vent with a continuous rise to outdoors, fit a flame arrestor, and terminate with a weatherproof hood at least one metre above the roof surface and away from air intakes.
On the dosing side, use PVDF or PE tubing rather than PVC, which becomes brittle in contact with hypochlorite. Fit a back-pressure valve and a pulsation damper, and take the pump suction at least 100 mm above the tank floor so sediment is not drawn into the dosing head.
Maintenance rhythm
| Item | Interval | Action |
|---|---|---|
| Brine concentration | Weekly | Refractometer check; top up salt, never let the brine go unsaturated |
| Softener | Weekly | Salt level, regeneration cycle, outlet hardness |
| Cell acid wash | 2 – 6 months | Dilute hydrochloric acid, per manufacturer procedure |
| Available chlorine test | Weekly | Titration or DPD against the design figure |
| Hydrogen detector test | 6 months | Calibration gas, alarm and interlock |
| Electrode inspection | 12 months | Coating condition; design life 5 years, practical 2 – 5 years |
Frequently asked questions
How long does the hypochlorite keep?
Seven to ten days is the working figure for full strength at 8 g/L. Beyond that you are dosing a weaker solution and the metering pump setting no longer reflects the dose. Size storage for a week and run the generator on a daily cycle rather than making a month of chemical at once.
Can the generator run on sea water?
Yes, with a cell designed for it. Sea-water electrolysis produces hypochlorite at lower concentration and requires corrosion-resistant wetted parts; the chlorine output per kWh is lower and chlorate formation is harder to control. It is common on ships and coastal plants, less so on inland municipal supply.
Does the installation need a permit?
In most jurisdictions on-site generation below a threshold capacity is treated as a water-treatment installation rather than a chemical plant, but the hydrogen vent, the room ventilation and the chemical storage all fall under local rules. Check with the authority having jurisdiction before the room is built, not after.
Send the peak flow, the target residual and the daily run hours, and we will size the generator, the softener and the storage tank as one package. Related reading: chlorine dioxide systems where chlorine is ineffective, and tank self-cleaning units for storage hygiene. Back to the product overview.