Tank Self-Cleaning Sterilizers
A storage tank is the weakest point in most building water systems. Water sits for hours, chlorine decays, the tank walls stay at ambient temperature and a biofilm forms on the wetted surface within weeks of commissioning. The bacteria that grow there are shed into the supply at exactly the moment demand peaks and the tank draws down. A tank self-cleaning sterilizer addresses that specific problem: it keeps the stored water moving through a disinfection chamber, so the tank contents are treated continuously rather than only on the way in.
Two configurations
The first is a side-stream unit. A small pump draws water from the tank, passes it through a reaction chamber where ozone or a micro-electrolysis cell acts on it, and returns it to the tank through a distributor that creates a slow rotation in the stored volume. Turnover is typically one to two tank volumes per day. Because the unit sits outside the tank, it can be serviced without entering the confined space, which is a decisive advantage for existing buildings.
The second is a submerged unit hung inside the tank through the manhole. It circulates water locally and treats it in an integrated chamber. It needs no external pipework and no pump room, but every service activity becomes a confined-space entry, and the unit competes for space with the inlet, outlet and overflow.
For tanks above about 50 m³, or for tanks that are already in service and difficult to enter, the side-stream arrangement is the practical choice. For small tanks in new buildings, the submerged unit is cheaper and simpler.
Sizing by volume, not by flow
The instinct is to size the unit like a filter, by the throughput of the supply main. That is the wrong basis. The load is the tank itself: its volume, its surface area and the rate at which chlorine decays in it. Sizing therefore starts from tank volume and target turnover.
| Tank volume | Circulation flow | Ozone output | Typical unit |
|---|---|---|---|
| 5 – 10 m³ | 1 – 2 m³/h | 2 g/h | LK-TS-10 |
| 10 – 30 m³ | 2 – 4 m³/h | 5 g/h | LK-TS-30 |
| 30 – 60 m³ | 4 – 8 m³/h | 10 g/h | LK-TS-60 |
| 60 – 120 m³ | 8 – 15 m³/h | 20 g/h | LK-TS-120 |
| 120 – 300 m³ | 15 – 30 m³/h | 40 g/h | LK-TS-300 |
Turnover of one to two volumes per day suits most buildings. Higher turnover improves mixing but does not proportionally improve water quality, because the limiting factor becomes the biofilm on the walls rather than the bulk water. Where the tank is large and the demand is low, a single unit with a longer run time is better than two small units cycling on and off.
Why ozone rather than chlorine
Ozone dissolves into the stored water, oxidises the organic film on the walls and decays within tens of minutes, leaving no taste and no disinfection by-products in the tank. Chlorine dosed into a tank does the opposite: it persists, it reacts with the organic matter to form trihalomethanes, and in a large tank the dose needed to reach the far wall produces an unacceptable taste at the outlet.
The trade is that ozone leaves no residual either. A tank unit therefore maintains tank cleanliness and controls bulk-water bacteria; it does not replace the residual disinfectant required in the distribution network. The correct arrangement is a small residual at the tank outlet plus continuous tank treatment, and the two must be commissioned together so that one does not mask a failure in the other.
Installation requirements
The return distributor matters as much as the generator. A single return nozzle creates a jet and a dead zone; a distributor with several nozzles arranged tangentially produces the slow rotation that keeps the whole volume moving. The nozzles should sit below the minimum water level so that ozone is not released into the headspace.
Vent the tank. Even with a submerged return, a fraction of the ozone leaves the water and accumulates under the tank cover. The vent must go outdoors, sized for the air change the tank needs, and must not discharge into a plant room or a stairwell. An ozone monitor in the tank room, interlocked to the generator, is a reasonable safeguard on any installation above 10 g/h.
Electrically, provide a dedicated circuit with earth leakage protection and bond the tank, pipework and unit to the same earth. Tanks are often the largest earthed mass in a building and potential differences between the tank shell and the pipework show up as corrosion at the connections, not as an obvious fault.
Operation and maintenance
| Item | Interval | Note |
|---|---|---|
| Tank inspection | 6 months | Sediment, wall film, corrosion at inlet |
| Sediment flush | 6 – 12 months | Drain and clean; the unit does not remove silt |
| Ozone generator service | 12 months | Dielectric, seals, cooling fan filter |
| Circulation pump | 12 months | Strainer clean, seal check |
| Water test | Quarterly | Total coliform, heterotrophic plate count, residual |
| Vent and monitor check | 12 months | Airflow, alarm function |
The unit does not remove sediment. Sand and rust that enter with the supply settle at the tank floor, and no amount of circulation will lift them; a periodic drain and manual clean is still required. What the unit prevents is the biofilm and the bacterial regrowth that follow if the tank is left alone for years.
Frequently asked questions
Can it replace chlorination in the tank?
No. It keeps the tank clean but leaves no residual in the water leaving it. Buildings with long internal networks, dead legs or low occupancy still need a residual disinfectant, whether from a small hypochlorite dosing set or from an on-site generator.
Is ozone safe inside a drinking water tank?
The dissolved ozone is consumed within the tank and the concentration in the headspace is what matters. With a submerged return, a sealed cover and an outdoor vent, headspace concentration stays far below occupational limits. Without a vent, it does not, which is why the vent is not optional.
How do we know it is working?
Two indicators: the heterotrophic plate count on a tank-wall swab, and the trend of residual chlorine at the outlet compared with the inlet. A tank that is being treated shows a stable, low wall count; an untreated tank shows counts rising through the summer. Bulk water samples alone will not show the difference, because the biofilm is on the wall, not in the sample bottle.