AOT for Hot-Water Loops and Legionella Control

Hot water is a hard duty for ordinary UV. As temperature rises, scale forms on the water side of the quartz sleeve and blocks UV-C transmission, so a reactor that validates perfectly on cold water quietly loses dose in a 55 °C recirculation loop. AOT — UV-driven TiO₂ photocatalytic oxidation — exists mainly to work around that problem.
What changes in the reactor
A specialised lamp outputs in the germicidal range and simultaneously excites a nano-TiO₂ photocatalyst coating. The excited coating generates hydroxyl radicals from water. Those radicals oxidise cell membranes and break down organic matter into smaller compounds, ultimately CO₂ and H₂O. Because the lamp is specified for stable output at elevated temperature, the unit keeps working where a conventional low-pressure sleeve would be scaling over.
The result is a combined physical and oxidative attack rather than nucleic-acid damage alone — see how the AOT mechanism works.
Where it gets specified
- Legionella control in domestic hot-water and heat-exchange systems — the most common driver.
- Heating circulation loops and industrial cooling-water circuits.
- Central air-conditioning chilled and condenser water.
- Fountains, landscape water and pools, where warm water and biofilm coincide.
Vendor literature typically claims broad-spectrum inactivation, complete mineralisation of organics to CO₂ and H₂O, continuous high-flow capability and intelligent control. Those are directional, not guarantees: radical yield depends on UVT, contact time, catalyst condition and water matrix. For a Legionella duty, ask for a test report on comparable water and a written cleaning or replacement schedule for the TiO₂ coating.
How it differs from the alternatives
Compared with storage tank disinfection units, which circulate ozonated water through a tank, an AOT reactor treats the loop itself in-line. Compared with chlorine dioxide or ozone dosing, it needs no chemical storage or on-site generation — but it also leaves no residual, so loop hygiene and temperature management remain part of the control strategy.
Specify water temperature, flow, UVT and the target organism. Those four numbers decide whether an AOT unit or a conventional UV reactor is the right answer.
Need a system sized for your water? Send us your flow rate, UV transmittance (UVT) and the target log reduction, and our engineers will specify the reactor and validated dose. Explore the product range or browse the Technical Library.