UV Reactor Installation and Commissioning Specification

A reactor is only as good as the water and the pipework around it. This is the commissioning specification we work to for pressurised in-line UV units.
What the unit contains
A low-pressure mercury lamp radiating at 253.7 nm, a fused-quartz sleeve, a stainless chamber, and a power/control package — ballast, cooling fan, hour meter, indicator lamps. Nothing exotic. The specification is what makes the difference between a validated dose and a guess.
Feed-water and site conditions
| Parameter | Limit |
|---|---|
| Turbidity | ≤ 5 NTU |
| Total iron | ≤ 0.3 mg/L |
| Colour | ≤ 15 degrees |
| Total coliforms / plate count | ≤ 1,000 /L; ≤ 2,000 /mL |
| Ambient temperature | > 5 °C |
| Relative humidity | ≤ 90% |
| Supply | 220 V ± 22 V, 50 Hz ± 2.5 Hz |
| Working pressure | ≤ 0.60 MPa (QL series) / ≤ 0.80 MPa (RZ series) |
| Head loss at rated flow | < 0.005 MPa |
A new 30 W lamp should read at least 90 µW·s/cm² irradiance, and factory delivered dose with the chamber filled should not be below 12,000 µW·s/cm². Dose is irradiance × time — the same equation behind fluence targets.
Installation
Leave more than 1.2 m at the lamp-withdrawal end and at least 0.6 m at the wall side, provide a drain nearby, and make sure earthing is correct. Four positions are acceptable: on the outlet of a elevated tank (with ≥ 0.5 m head above the reactor), on a pump discharge with a pressure tank, on a pump discharge without one, or on a pump suction line. In every case the rated flow must cover the pump group’s maximum output, and a higher-pressure chamber must be specified where pump head exceeds the working rating.
Operating routine
Allow 5–10 minutes of stabilisation after striking before judging output. Increase effluent monitoring as the hour meter approaches rated lamp life. Keep voltage and lamp power stable. Clean the chamber, lamp and sleeve with alcohol on a soft cloth — never touch cleaned quartz with bare hands. Wear tinted UV goggles and gloves during any inspection. And remember: with no residual, the downstream pipework must be constructed and managed so the water cannot be recontaminated.