WTS Tank Disinfection Units: Models and Product Standard

WTS Tank Disinfection Units: Models and Product Standard — Longcom technical note

The WTS series is the standardised form of a storage tank disinfection system. Three models cover small to medium tanks; selection is by tank volume and turnover, not by pipe flow.

Model table

Model Power Ozone Tank volume Head / controller Type
WTS-2A 405 W 4 g/h < 20 m³ 25 kg / 18 kg Single-head, internal
WTS-2B 745 W 8 g/h 20–40 m³ 50 kg / 25 kg Twin-head, internal
WTS-2W 405 W 4 g/h < 20 m³ — / 45 kg External

Supply is 220 V for both the generator and the energy-release head. Installation dimensions (mm): WTS-2A Ø400 × 520, A1 380, B1 200, H1 560; WTS-2B Ø400 × 520, A1 430, B1 200, H1 650; WTS-2W Ø300 × 500, A1 380, B1 200, H1 560. Convert volumes to US gallons when specifying for North American projects — 20 m³ is roughly 5,300 US gal.

What the product standard requires

  • Wetted materials comply with GB/T 17219-1998 for drinking-water contact safety.
  • Smooth surfaces, no pits, peeling, crevices or dead zones, so stagnant layers cannot seed microbial growth.
  • Electrical insulation parts in epoxy glass cloth laminate, 15–30 kV/mm dielectric strength.
  • Interchangeable parts within a model.
  • Insulation resistance ≥ 5 MΩ between supply inlet and enclosure; electrical safety per GB/T 18216.1-2012.
  • Timer default 30 minutes on, 5 minutes off, adjustable to the site’s demand profile.
  • Circulation pump run-in for 12 hours with power and water before acceptance, no tripping.
  • Pipe joints gas-tight, pressure rating 0.4 MPa.
  • Inlet is municipal tap water used for secondary supply; outlet to meet the drinking-water disinfectant/equipment safety evaluation specification.
  • Operating environment 5–40 °C, AC 220 V ± 20 V, 50 Hz.

For siting, the external-vs-internal decision and the seven installation rules, see the installation guide. Note that ozone leaves no persistent residual, so tank turnover and circulation coverage are the real design variables.

Need a system sized for your water? Send us your flow rate, UV transmittance (UVT) and the target log reduction, and our engineers will specify the reactor and validated dose. Explore the product range or browse the Technical Library.

Condensed from our Chinese technical article. Read the full Chinese version.

UV disinfection, storage tank treatment, on-site hypochlorite (OSHG), chlorine dioxide and ozone systems for municipal, high-rise booster and industrial water.

Contact

Hotline +86 4008-780-280

Mobile / WhatsApp +86 130 1601 3265

R&D center, Guangzhou +86 20-2818 5170

Plant in Xianning, Hubei · R&D in Guangzhou, Guangdong