Ultraviolet is the 10–400 nm slice of the electromagnetic spectrum, and it is subdivided by behaviour rather than by neat boundaries. UVA runs 315–400 nm, UVB 280–315 nm, UVC roughly 100–280 nm. Only the last band is strongly germicidal.

Why 253.7 nm

Microbial DNA absorbs most strongly around 260–265 nm. Low-pressure mercury vapour lamps happen to concentrate nearly all their output at 253.7 nm — close enough to that peak to be extremely efficient. That is why the overwhelming majority of in-line UV disinfection systems use low-pressure or low-pressure high-output lamps: one wavelength, very high conversion efficiency, long life.

Medium-pressure lamps are different. A medium-pressure UV system emits a continuous spectrum from about 200 to 400 nm at much higher power per lamp. The extra wavelengths are not wasted — shorter bands photolyse chloramines and help reduce TOC, which is why MP systems are common on pools and process water even though they are less electrically efficient for straight disinfection.

One number people confuse

185 nm is not a germicidal line; it generates ozone from oxygen. Lamp makers control it by doping the quartz with titanium to cut off transmission below about 200 nm. That is how “ozone-free”, “ozone-producing” and “high-ozone” lamps are made from otherwise similar tubes. For water reactors, ozone-free lamps are the norm.

Lamps age even while glowing

Output declines with hours. Low-pressure lamps are typically rated 8,000–12,000 hours; a lamp that still looks bright may already be below the fluence needed. Design dose is always specified at end of lamp life with a fouling allowance on the sleeve, and verified with a UV intensity sensor rather than by eye.

So the answer is 253.7 nm for most systems, a broad 200–400 nm band for medium-pressure duties, and a firm distinction between the two. If a supplier quotes wavelength without naming lamp type, ask again.

Need a system sized for your water? Send us your flow rate, UV transmittance (UVT) and the target log reduction, and our engineers will specify the reactor and validated dose. Explore the product range or browse the Technical Library.

Condensed from our Chinese technical article. Read the full Chinese version.

UV disinfection, storage tank treatment, on-site hypochlorite (OSHG), chlorine dioxide and ozone systems for municipal, high-rise booster and industrial water.

Contact

Hotline +86 4008-780-280

Mobile / WhatsApp +86 130 1601 3265

R&D center, Guangzhou +86 20-2818 5170

Plant in Xianning, Hubei · R&D in Guangzhou, Guangdong