UV Sterilizer Standard Technical Requirements

UV sterilizer technical requirements per national standards
GB standard requirements for UV sterilizer design and installation.

1. Operating environment conditions

The sterilizer should work normally under the following conditions.

1.1 Inlet water quality

Parameter Limit
Chroma (color) ≤15 degrees
Water temperature ≥5 °C
Total coliform ≤1,000 CFU/L
Total bacterial count ≤2,000 CFU/mL

1.2 Air environment

Maximum relative humidity ≤90% (equivalent to air at 20 °C ±5 °C).

1.3 Power supply

Mains power supply as specified for the equipment.

2. Basic technical requirements

  1. The design of the sterilizer shall comply with GB 8988 (Safety requirements for electronic and related equipment operated from the mains and for similar general purposes).
  2. The sterilizer shall be manufactured according to drawings and technical documents approved through the technical management procedure.
  3. Parts of sterilizers of the same model shall be interchangeable.
  4. Surfaces of the sterilizer exposed to UV radiation shall be polished.
  5. The working pressure of the pressure-bearing cylinder shall not be less than 0.60 MPa, and the test pressure shall not be less than 0.90 MPa.
  6. A baffle (flow guide plate) should be provided inside the cylinder or chamber.
  7. The installation of straight-tube quartz low-pressure mercury UV lamps shall comply with YY/T 0160 (Straight-tube quartz low-pressure mercury disinfection UV lamps).
  8. Where environmental requirements are strict, low-ozone lamps should be selected first to reduce ozone pollution of the environment.
  9. Lamps shall be arranged so that the UV intensity distribution over the irradiated surface is uniform.
  10. The sterilizer shall have a lamp-on indicator, a cumulative operating time indicator, or a relative indication of UV irradiance intensity.
  11. Lamps shall be separated from the water by a quartz glass sleeve; the transmittance of the quartz sleeve at 253.7 nm shall be greater than 85%.
  12. Low-voltage electrical components selected for the sterilizer shall meet the technical requirements of the corresponding products.
  13. The sterilizer shall be provided with inlet and outlet pipes, a drain pipe and a sampling pipe. Where a drain pipe cannot be fitted on the sterilizer, it may be installed on the connecting pipework at an equivalent position.
  14. The specifications of the sterilizer and the diameters of its inlet and outlet pipes should be selected according to the table.
  15. Under the inspection requirements of this standard, a sterilizer fitted with new lamps shall show a measured UV irradiation dose of not less than 12,000 µW·s/cm² (with the chamber filled with water); a sterilizer in normal operation shall show not less than 9,000 µW·s/cm².
  16. Under the operating conditions of this standard, at the rated disinfection flow, the bacteriological indicators of the outlet water shall comply with GB 5749 (Standards for Drinking Water Quality).
  17. Materials of the sterilizer shall comply with GB/T 17219 (Standard for safety evaluation of equipment and protective materials in drinking water distribution systems). 304L or 316L stainless steel should be used.
  18. The head loss of the sterilizer operating at the rated disinfection flow shall be less than 0.005 MPa.

3. Appearance requirements

  1. The equipment surface shall be coated evenly with a uniform color, free of runs, blisters, paint misses or peeling.
  2. The exterior shall be neat and free of obvious hammer marks or unevenness; instruments, switches, indicator lights and nameplates on panels shall be firmly and squarely mounted.
  3. Welding of the enclosure and frame shall be firm, with no obvious deformation or burn-through defects.

4. Construction and installation points

  1. Do not install the UV unit immediately downstream of a pump outlet, to prevent pump-stop water hammer from damaging the quartz sleeves and lamps.
  2. Install the UV unit strictly according to the inlet and outlet flow directions.
  3. The UV unit should have a foundation raised above the building floor; the foundation shall be at least 100 mm above floor level.
  4. The UV unit, its connecting pipes and valves shall be firmly supported; the unit must not carry the weight of pipework or fittings.
  5. Install the unit for easy removal, inspection and maintenance; no material affecting water hygiene may be used at pipe connections.

5. Applicable standards

5.1 Product standards

  • QB/T — UV Sterilizer
  • GB/T — UV Disinfection Equipment for Urban Water Supply and Drainage
  • CJ/T — UV Sterilizer for Drinking Water

5.2 Engineering standards

  • GB — Code for Design of Building Water Supply and Drainage
  • GB — Code for Design of Outdoor Drainage Engineering
  • GB — Discharge Standard of Pollutants for Municipal Wastewater Treatment Plants
  • GB/T 18920-2002 — Reuse of Urban Recycling Water: Water Quality Standard for Urban Miscellaneous Use
  • GB 50335-2002 — Design Code for Wastewater Reclamation and Reuse Engineering (with commentary)
  • GB 50242-2002 — Code for Acceptance of Construction Quality of Building Water Supply, Drainage and Heating Works

5.3 Related standard drawings

  • 02SS104 — Selection and Installation of Secondary Water Supply Disinfection Equipment

6. UV bands and germicidal effectiveness

By biological effect, ultraviolet is classified into UV-A (320–400 nm), UV-B (275–320 nm), UV-C (200–275 nm) and vacuum UV. Water treatment actually uses the UV-C band, in which the region around 260 nm has been proven to have the highest germicidal efficiency.