Ozone Disinfection and Bromate: What Bromide-Rich Sources Require

Ozone disinfection has clear strengths: powerful oxidation, fast inactivation, no trihalomethanes, and improvement of colour, odour and taste. But it carries an easily overlooked hidden risk — when the source water contains bromide, ozone oxidises it to bromate, whose GB 5749 limit is 0.01 mg/L, among the strictest in drinking-water regulation. Many projects size ozone output and contact time at design stage and only discover bromate exceedance in production testing — at high correction cost.
1. How bromate forms
Raw water naturally contains bromide ions (Br⁻). Ozone, and the hydroxyl radicals it produces, oxidise bromide stepwise: first to hypobromous acid and hypobromite, then on to bromate (BrO₃⁻). The chain is driven by ozone dose and contact time: higher dose, longer contact and higher pH all increase bromate formation.
Once formed, bromate is very hard to remove by conventional treatment — coagulation, sedimentation and filtration are essentially ineffective; only activated-carbon adsorption or biological reduction can cut it. This problem must be engineered out at design stage, not treated afterwards.
2. Limits and health risk
| Item | Requirement | Note |
|---|---|---|
| Bromate limit | 0.01 mg/L (GB 5749) | Among the strictest limits in drinking-water regulation |
| Bromide assessment threshold | Above ~100 μg/L, evaluate | Common in coastal, seawater-intruded and mine waters |
| Ozone dose | Typically 0.5–2 mg/L for drinking water | Correlates positively with bromate formation |
Bromate is classified as a possible carcinogen; long-term intake risk depends on concentration and duration. For water suppliers this is a one-strike parameter — a single exceedance means non-compliance, with no middle ground.
3. Which sources are high risk
- Coastal groundwater — seawater intrusion raises bromide; common along the south and east coasts
- Mine water and deep groundwater — some geologies carry a high bromide background
- Salinity-affected surface water — estuary zones see bromide fluctuate with tidal intrusion
- Reclaimed and industrial reuse water — complex sources may carry more bromide than conventional ones
The check is simple: test raw-water bromide at design stage, and sample across salt-intrusion and wet/dry seasons. A single dry-season measurement usually understates the risk.
4. Six control paths
- Cut ozone dose and contact time. Take the low end that still meets disinfection and oxidation targets; prefer “low dose, multiple injection points” or “main ozone + final chlorination” over a single high dose. The most economical option.
- Ammonia suppression. Small ammonia doses (forming chloramine or reacting with hypobromous acid) suppress bromate, but interfere with disinfection and residual control. Jar-test the dosing point and ratio, and mind ammonia’s own nitrification risk in the network.
- Control pH. Bromate formation slows at lower pH and can be moderated to suit the water — but not at the cost of network corrosion control.
- GAC or BAC downstream. Granular activated carbon adsorbs some bromate, and biologically active carbon can reduce it microbially — a common end-of-train safeguard, but with real replacement and backwash cost.
- Change the disinfection process. For small flows with high bromide, UV + trace chlorine avoids the oxidation path entirely — at the cost of losing ozone’s taste, odour and organic improvement.
- Source control. Switching sources during salt-intrusion periods, moving the intake, or adding storage to buffer quality is often cheaper than end-of-pipe treatment.
5. How to verify performance
Verification has three steps. First, test raw-water bromide to decide whether the assessment process is triggered. Second, run bench or pilot tests at the actual dose and contact time to map bromate formation and find the dosing window where disinfection passes and bromate stays under limit. Third, test regularly in production — covering at least the salt-intrusion and high-temperature seasons.
For analysis, bromate is measured by ion chromatography with detection limits adequate for the 0.01 mg/L judgement; field rapid tests are for screening only, not acceptance.
6. Off-gas and safety matter as much as bromate
While controlling bromate, do not neglect the ozone system’s own safety items. Ozone is toxic; off-gas from the contact columns must pass through a destructor — typically thermal-catalytic (300–350 °C) or catalytic decomposition. Direct discharge accumulates in the equipment room and corrodes it. Fit the destructor with temperature or concentration monitoring, alarm on failure, and interlock it with the generator.
Contact-column design drives both efficiency and safety: counter-current water–gas contact, sufficient contact time (usually 10–15 minutes), an off-gas collection port at the top, and stable water level and pressure. If the level swings, ozone escapes with the vent gas — wasting output and raising leakage risk. The room needs an ozone alarm set to the occupational exposure limit, with the fan interlocked to the generator.
Ozone also attacks rubber, some plastics and copper: choose ozone-resistant materials for piping and seals. After ozonation, allow a short detention before the clearwell so residual ozone decomposes and does not affect downstream processes or network materials.
7. FAQ
Does ozone always form bromate? No. Significant formation requires both bromide in the source and sufficient dose/contact time. Low-bromide sources (most inland surface waters) carry low risk — but test and confirm at design stage anyway.
Is activated carbon the only fix for bromate exceedance? It is the common one, but the more economical route is cutting the ozone dose at source, optimising injection points and contact, and combining ammonia dosing or source switching where possible. Carbon suits end-of-train assurance, not a sole strategy.
Is UV safer than ozone here? UV does not oxidise bromide, so it forms no bromate — a real advantage. But it has no residual effect and does not improve taste or odour, so it usually pairs with trace chlorine for network residual. The choice depends on water-quality targets and network conditions.