Chlorine Dioxide By-Product Control: Chlorite and Chlorate

One reason chlorine dioxide is recommended for drinking water is that it does not generate trihalomethanes the way chlorine does. That does not mean it is by-product free: chlorite and chlorate are the two main ClO₂ by-products, both limited to 0.7 mg/L under GB 5749. In real projects, exceedances are rarely the fault of chlorine dioxide itself — they trace back to poor generator conversion efficiency, unbalanced chemistry, or overdosing. Control those three paths and the by-products stay under control.
1. Where the by-products come from: three paths
- Incomplete conversion. Sodium chlorite that has not fully converted to chlorine dioxide enters the water directly as chlorite. A 90% conversion rate means one part in ten of the feed stays in the water as chlorite — the most common source.
- Unbalanced chemistry and conditions. Insufficient hydrochloric acid raises pH and the reaction stalls at intermediates; reaction temperature too high or too low, or insufficient residence time, increases side reactions that form chlorate. Feed concentration drift (sodium chlorite solution decomposing in storage) also breaks the ratio.
- Overdosing and photolysis. Excess chlorine dosed to hold a residual decomposes in the water, part of it becoming chlorite and chlorate. ClO₂ solution also decomposes in light — especially when storage tanks are not shielded.
2. Limits and interpretation
| Parameter | GB 5749 limit | Common causes of exceedance |
|---|---|---|
| Chlorite | 0.7 mg/L | Low conversion, overdosing, residual liquor carried into the water |
| Chlorate | 0.7 mg/L | High reaction temperature, chlorate impurities in the feed, ClO₂ decomposition |
| ClO₂ residual | 0.1–0.8 mg/L at the plant; ≥0.02 mg/L at the network end | Under-dosing or fast network decay |
Distinguish residual from by-products: residual reflects disinfection capacity, by-products are the cost of the reaction. They are not simply traded off against each other — raising conversion efficiency improves both at once, whereas simply dosing more only raises the by-products.
3. Four actions to push chlorite down
- Raise conversion efficiency. The fundamental fix. Control acid excess and reaction temperature per the manufacturer’s requirements and test the product liquor and residual liquor regularly; conversion above 90% naturally cuts chlorite carry-over. Every 5-percentage-point gain reduces what enters the water proportionally.
- Keep residual liquor out. Generator residual liquor must be discharged separately or returned for treatment — never mixed into the dosing stream. Some simple units have no liquor separation and by-products accumulate over time.
- Dose in a closed loop against residual. Hold the plant-exit residual in a sensible band of 0.2–0.4 mg/L rather than “the higher the safer”. Higher residual means more decomposition into chlorite. Closed-loop control markedly cuts overdosing.
- Add a reduction step if needed. Some plants dose ferrous or sulphite reducers at the network end or in the clearwell to reduce residual chlorite to chloride. This raises chemical cost and sludge, and is generally reserved for high-bromide sources with heavy by-product pressure; run jar tests to size it.
4. Controlling chlorate
Chlorate formation is strongly temperature-dependent. Above the manufacturer’s recommended reaction temperature, chlorate formation accelerates; impure sodium chlorite feed with chlorate contamination carries it in directly. Controls: hold reaction temperature and cooling-water flow per the manufacturer’s specification; source feed of stable purity with test certificates; avoid long high-temperature standby of the generator.
An overlooked source is solution storage: ClO₂ decomposes under light and heat and chlorate climbs with it. Storage tanks must be shaded and cool, and storage limited to 1–3 days — generate and use.
5. The other by-product family: bromide-rich sources
Coastal areas, seawater-intruded groundwater and some mine waters carry elevated bromide. Chlorine dioxide oxidises bromide to hypobromous acid, which forms brominated THMs and other brominated by-products — a different path from ozone’s bromate formation, but one that must be assessed at design stage. Test raw-water bromide first: above 100 μg/L, run specific testing for brominated by-products and allow margin in dose and contact time.
Note that chlorine dioxide forms far less bromate than ozone; the real risk is brominated organics. Where bromide and organics are both high, chlorine dioxide alone cannot fully avoid the issue — combine with activated-carbon adsorption or reconsider the disinfection process.
6. Monitoring and two common misreadings
Accurate quantification of chlorite and chlorate uses ion chromatography; field screening can use colorimetric methods. Note that when measuring residual chlorine by DPD, both chlorine dioxide and chlorite interfere with the reading — without separation, you can conclude “residual OK but disinfection poor” or a falsely high residual.
- Misreading 1: treating residual as disinfection performance. ClO₂ residual readings carry many interferences; judge against microbial results and by-product data together, never one number alone.
- Misreading 2: responding to exceedance by dosing more reducer. Reducers only treat chlorite already formed; they do nothing for conversion efficiency. Without fixing generation conditions, reducer use and cost keep climbing.
7. FAQ
Does chlorine dioxide produce THMs? Far less than chlorine — one of its main advantages. But it produces chlorite and chlorate, both limited at 0.7 mg/L, and both need control.
Chlorite is over the limit — what to fix first? Check conversion efficiency and chemistry ratio first, then whether dosing is excessive, then whether storage or residual liquor is contaminating the water. Most exceedances come from low conversion or overdosing, not the chemicals themselves.
Can reducers be used long term? As a transition or auxiliary measure, yes — but they add chemical cost and sludge and do not fix the root cause. Optimise generation conditions first, then decide whether a reduction step is still needed.