UV Disinfection Modules in Water Supply Treatment

Abstract: Drawing on engineering examples of UV sterilizer processes in water supply treatment, this paper investigates and summarises the problems arising in these projects and puts forward reasonable recommendations.
Since the discovery in the early 20th century that chlorine can inactivate pathogenic microorganisms in water, chlorination has been widely used in water supply treatment and became one of the important technological advances protecting human health in the 20th century. With social development, however, conventional disinfection methods now face serious new challenges. These fall mainly into three areas. First, chlorine-resistant pathogenic microorganisms exist in drinking water, the most typical being Cryptosporidium and Giardia, commonly known as the “two parasites”. Second, there is the problem of disinfection by-products, mainly trihalomethanes (THMs), haloacetic acids (HAAs) and bromate. Third, there is the issue of public safety: liquid chlorine used for disinfection carries a risk of leakage during production, transport, storage and use.
China’s Standards for Drinking Water Quality (GB 5749-2006), implemented in 2007, sets very strict requirements for disinfection-related water quality indicators, including bacteriological indicators, the “two parasites”, disinfection by-products and disinfectant residuals. As a non-chemical disinfection technology with a broad spectrum of effective disinfection and no formation of disinfection by-products, UV has been adopted rapidly over the past decade in developed countries in Europe and North America.
China completed its first demonstration drinking-water UV disinfection project, designed and commissioned together with the purification process, in 2009: Phase III of the Tianjin Development Zone Water Plant (150,000 m³/d). Other plants now formally using UV sterilizer processes in China include the Shanghai Linjiang Water Plant (600,000 m³/d), Phases I and II of the Tianjin Development Zone Water Plant (175,000 m³/d), the Jinan Yuqing advanced water treatment project (210,000 m³/d) and the Daqing water supply project (50,000 m³/d). Water plants using UV disinfection abroad include the Victoria plant in Canada (580,000 m³/d), the Seattle plant in the United States (680,000 m³/d), the PWN Andijk plant in the Netherlands (100,000 m³/d), the Berenplaat plant in the Netherlands (470,000 m³/d) and the Catskill/Delaware reservoirs in New York (8.3 million m³/d), all of which use UV sterilizer processes.
Continuing pollution and deterioration of drinking water sources in China, together with the implementation of new drinking water quality standards, have raised concern about the quality of drinking water today. Since every disinfection process has its own limitations, the following sections compare the various disinfection processes, list a number of implemented UV sterilizer projects, and set out the related problems and recommendations.
1. Disinfection methods in common use today
1.1 Chlorine and chloramine disinfection
Chlorine disinfection kills bacteria mainly through the oxidising action of hypochlorous acid; it is less effective against viruses and parasite eggs in water. Its principal problem is that active chlorine reacts with organic matter in water to form disinfection by-products such as trihalomethanes and haloacetic acids. In addition, the taste of water disinfected with chlorine is poorer than with other disinfectants.
The mechanism of chloramine disinfection is generally considered to be the same as that of chlorine, but it reduces the formation of THMs during disinfection, persists longer in the distribution network, and is more effective than chlorine at controlling bacterial regrowth and biofilms in the network.
What chlorine and chloramine disinfection have in common is a very poor removal efficiency for Giardia and Cryptosporidium in water.
1.2 Chlorine dioxide disinfection
Chlorine dioxide is a strong oxidant with good adsorption and penetration of bacterial cell walls. It can effectively oxidise cellular enzyme systems and rapidly control the synthesis of enzyme proteins, so under the same conditions it shows a higher removal efficiency than chlorine for most bacteria.
Because every process for producing chlorine dioxide generates a certain amount of free chlorine, chlorine dioxide disinfection still carries the possibility of forming chlorinated organic disinfection by-products, although at concentrations far lower than those from liquid chlorine. The main by-products of chlorine dioxide disinfection are chlorite and chlorate, both of which are potentially hazardous to human health.
1.3 Ozone disinfection
The advantages of ozone disinfection are clear: pathogenic bacteria, and especially the chlorine-resistant Cryptosporidium and Giardia, are killed effectively at low dosages, and the taste of the disinfected water is markedly better than that of chlorinated water. The main problems to be solved are the control of disinfection by-products (formaldehyde and bromate ions). Ozone generation equipment is also large, expensive and complex, and requires a high level of operational management. At the same time, ozone decomposes easily, so ozone disinfection alone cannot guarantee a sustained bactericidal effect and can readily lead to bacterial regrowth.
1.4 Membrane disinfection
Membrane disinfection separates bacteria from the water, effectively preventing dead bacteria from becoming a source of pyrogens. Its advantages include excellent treated water quality, no consumption of chemicals or only small quantities, low energy use, low operating costs, disinfection performance unaffected by raw water quality, and stable effluent quality. The main problems are membrane fouling and the deterioration of filtered water quality once membrane integrity is damaged.
1.5 UV disinfection
Electromagnetic waves at wavelengths of 250–270 nm alter the nitrogen-containing heterocyclic substances in the two important genetic materials DNA and RNA, creating new bonds between adjacent nucleosides to form dimers. This prevents microorganisms from replicating themselves and achieves disinfection.
The advantages of UV disinfection technology are clear: at a very low disinfectant dose and a short contact time it can effectively kill pathogenic bacteria, and no disinfection by-products are produced in the treated water.
The main problem facing UV disinfection is that there is no residual chlorine in the disinfected water, so bacteria can readily regrow in the distribution network and cause secondary pollution.
2. Engineering examples of UV sterilizer processes
2.1 Japan Gulch water plant, Victoria, Canada
Victoria is the capital of the Canadian province of British Columbia and a famous tourist destination, located on scenic Vancouver Island with a mild climate. The Japan Gulch plant has a treatment capacity of about 580,000 m³/d and is the second-largest municipal water plant in British Columbia, serving a population of about 320,000. The raw water quality is very good (turbidity below 1 NTU) and the plant has only a disinfection process. Before the retrofit, chloramination was used, with a disinfection target of 99.99% virus removal and a total residual chlorine level maintained at 1 mg/L in the finished water. Between October 1994 and May 1995, more than 100 acute cases of parasite transmission caused by Toxoplasma in drinking water were reported on Vancouver Island, with approximately 2,900–7,000 residents infected. In 1995 the government began considering stricter disinfection standards for the Japan Gulch plant to improve water safety, requiring removal rates of 99.99% for viruses, 99% for Giardia and 99% for Cryptosporidium. As the existing process could not meet the new targets, a three-stage, multi-barrier combined disinfection process was proposed: the first stage is UV, mainly for parasite control; the second is chlorine, mainly for bacteria and viruses; and the third is chloramine, to maintain a residual chlorine level in the distribution network. This multi-barrier strategy broadens the spectrum of microbial disinfection and guarantees the safety of the water supply.
The plant was designed for a peak flow of 580,000 m³/d, with a minimum UV transmittance of 85% and a UV dose above 40 mJ/cm².
2.2 Cedar water plant, Seattle, United States
The Cedar plant is one of two water plants serving Seattle and is managed by Seattle Public Utilities, with a treatment capacity of 680,000 m³/d. In 1992 the city suffered a severe water shortage, and coliform bacteria exceeded the standard in 11 of the indicators monitored in the Cedar plant’s raw water. To achieve 99% removal of Cryptosporidium, 99.99% removal of Giardia and 99.999% removal of viruses, a combined ozone and UV multi-barrier disinfection process was finally selected. Ozone is used to remove 99.99% of Giardia and 99.999% of viruses, and also to address seasonal odour problems caused by algae; UV is used to remove 99% of Cryptosporidium and to control bacteria and viruses, providing a second disinfection barrier. The ozone and UV dosages were established according to this division of responsibilities: the UV disinfection dose was set at 40 mJ/cm², with a UV transmittance of 90%.