Key Factors for UV Disinfection of Wastewater

Open-channel UV disinfection system for wastewater
Peak flow and UV transmittance drive channel design

Several water-quality and hydraulic factors must be considered when applying UV disinfection to wastewater.

1. UV transmittance (UVT)

UV transmittance reflects how deeply UV light penetrates a liquid and is an important basis for sizing a UV disinfection system. UV transmittance decreases as the water layer becomes thicker, and also falls when the wastewater contains soluble chemicals that absorb UV. In terms of disinfection performance, a reduction in irradiation intensity has a greater effect than water clarity and can be compensated for by extending contact time or increasing the number of UV lamps in the system.

In design practice, the general requirement is [] (as printed in the source), together with a flexible automatic control system that monitors the incoming water quality at all times. The transmittance of a 1 cm water sample is ≥65%; as transmittance varies, the automatic control system can adjust UV lamp output or the number of lamps in operation to maintain good disinfection.

2. Suspended solids (SS) and particle size

Water-quality parameters such as suspended solids reflect the degree to which light is scattered by suspended matter; they depend on particle size, shape and refractive index, and affect UV transmittance. Their influence on UV disinfection appears mainly in two ways: 1) suspended particles absorb and scatter UV, reducing the UV intensity transmitted through the water and therefore the dose reaching the surface of microorganisms; and 2) suspended particles shield microorganisms, protecting them inside particles from UV damage and making them difficult to disinfect. As flow increases, the influence of turbidity and suspended matter on disinfection becomes more pronounced. The influent concentration of wastewater to be disinfected by UV must therefore be strictly controlled; SS is generally recommended not to exceed 20 mg/L. Particle size also affects UV penetration. Particles smaller than 10 µm are easily penetrated by UV and require a low UV dose; particles between 10 and 40 µm can be penetrated but need a higher UV dose; particles larger than 40 µm are difficult to penetrate and require a relatively high UV dose.

3. Hydraulic conditions of the reactor

Most disinfection systems use an open-channel configuration, seeking a uniform velocity field in the inlet and outlet channels, but in practice the flow pattern differs considerably from the ideal. When the water volume suddenly increases, UV contact time becomes shorter and a stronger UV dose is required. UV disinfection systems are therefore generally designed on the basis of the maximum peak flow.

Open-channel UV disinfection system

For example, a wastewater treatment plant in Dalian ( /d) was designed on a continuous inflow of /h. In actual operation, however, the upstream process of the UV disinfection channel could not deliver 24 h continuous outflow, so the design expectation was not met. Flow fluctuation during operation damaged the UV disinfection system and made it unstable: at peak flow (instantaneous maximum flow of /h) the sterilisation result failed to meet the standard; frequent lamp starts shortened lamp life; the water-level control device operated frequently; and sleeve fouling intensified. To address these problems, the UV system was modified: one new UV disinfection channel was built and the original channel was kept as a maintenance bypass. The new system was designed for a maximum flow of 4,500 m³/h (printed as “4 500 m( /h)”), with additional UV modules and lamps. The water-level control device was changed from an unpowered automatic control gate to a fixed overflow weir, so that at zero flow the lamps remain fully submerged and stay lit continuously for 24 h without frequent starting, while at maximum flow the water depth over the weir does not exceed the effective sterilisation range of the lamps.

4. Inorganic ion concentration

Iron is a strong UV absorber, and iron in water reduces UV transmittance. Effluent from treatment plants using ferric salts as coagulant contains relatively high Fe3+ concentrations, which may affect subsequent UV disinfection. Ferric salts at low concentrations have a noticeable weakening effect on UV inactivation of E. coli, but as the UV dose increases this effect gradually becomes less clear. Studies indicate that the Fe3+ concentration at which UV sterilisation begins to be affected is 0.057 mg/L. In addition, the presence of ferric salts tends to accelerate fouling of UV lamp sleeves. For water plants that use ferric salts in treatment or whose wastewater has a high ferric-salt content, the iron factor should be considered when choosing UV disinfection. Humic acid is also a strong UV absorber: as its concentration rises, the removal rate of E. coli drops markedly (especially at a concentration of 50 mg/L), while at low concentrations (<10 mg/L) the effect on UV disinfection can be neglected. As the UV dose increases from low to high, the degree to which humic acid at different concentrations reduces E. coli inactivation gradually diminishes, and the removal rate gradually approaches that of the control.

5. Types and numbers of microorganisms

Wastewater disinfection focuses on killing enteric bacteria that cause waterborne diseases. UV kills bacteria, viruses, fungi and spores alike. In general, Gram-negative bacilli are the easiest to kill with UV, followed by Staphylococcus, Streptococcus and bacterial spores; fungal spores are highly resistant, while viruses are less resistant than bacterial spores. To achieve the same sterilisation result, microorganisms that are insensitive or highly resistant to UV require a larger irradiation dose.