UV Sterilizers for Wastewater Treatment Upgrades

If treated wastewater is discharged to too low a standard, the effluent can become a source of pollution in its own right. Municipal wastewater treatment plants are being required to upgrade, moving beyond Class I-B toward stricter Class I-A limits. This article reviews why UV disinfection is well positioned for these upgrades and which equipment features matter.
1. Tightening discharge standards drive upgrades
All regions are preparing to raise pollutant discharge standards for municipal wastewater treatment plants. Beyond meeting current limits, plants need upgrading and retrofitting. The new requirements are stricter than Class I-B and build on Class I-A, and will be phased in. Raising wastewater standards is not an isolated case: Guangdong, Beijing and Tianjin have already tightened limits to Class III to Class IV surface-water quality. The national Discharge Standard of Pollutants for Municipal Wastewater Treatment Plant was revised 13 years after publication, with comments solicited last year; the number of controlled pollutant items rises from 62 in the current standard to 103 in the new one. Even before the new national standard is formally issued, the stricter Class I-A limits are being applied more widely. New, rebuilt and expanded municipal wastewater treatment facilities must meet Class I-A in full. The Water Pollution Prevention and Control Action Plan published by the State Council also requires municipal treatment facilities in sensitive areas (key lakes, key reservoirs and coastal catchments) to meet Class I-A by the end of 2017, and new facilities in built-up areas where water quality fails Class IV surface-water standard to apply Class I-A.
2. Comparison of disinfection technologies
Processes able to meet upgrade needs include fiber disc filters, precision filters, activated-sand filters, aerated biological filters, sedimentation and UV sterilization. Upgrade costs are quoted at 50–250 yuan per cubic metre. There are about 4000 wastewater treatment plants in China, of which nearly 1000 have not yet reached Class I-A; of more than 300 plants in the Pearl River Delta, only about 50 meet Class I-A. The upgrade market is therefore substantial.
Deep treatment for upgrades includes coagulation, filtration, disinfection and natural purification. Commonly used disinfection processes include halogen disinfection (chlorine), oxidation (chlorine dioxide, ozone, peracetic acid) and radiation (UV, gamma rays). Liquid chlorine has been widely used as an inexpensive disinfectant, but chlorine reacts with organic matter in water and interferes with disinfection; reaction by-products such as halogenated hydrocarbons, chloroform, trihalomethanes and polychlorinated biphenyls are toxic to humans and livestock, and many are carcinogenic, teratogenic and mutagenic. Many countries and local governments now restrict chlorine and its derivatives, and environmental and labor protection authorities in some parts of China also control its use.
Chlorine dioxide disinfection is being accepted and recognized in China, but it must be generated on site and only about 20% of it is effective in the disinfection process. Chlorine dioxide generators are also small, so applying them to plants with high chlorine demand remains a problem. For these reasons, UV sterilizers have broad application and market prospects in wastewater plant upgrades.
3. Advantages of UV systems
With continuing progress in UV disinfection technology and increasingly intense international competition, UV lamp life has passed 15000 hours in high-tech products made by only a few countries, while prices have dropped considerably. UV disinfection is now applied in wastewater treatment at home and abroad and is becoming a better alternative to conventional liquid chlorine. Liquid chlorine systems require more civil works and facilities than UV equipment; UV treatment also has advantages in running cost, simpler operation and easier maintenance.
The successful operation of any UV system depends on maintenance frequency and ease of repair. Advanced design simplifies these requirements: long-life UV lamps, reliable and durable electronic ballasts, lamp racks and effective automatic cleaning deliver the desired combination of time savings, lower cost, energy efficiency and simple maintenance.
4. Selecting UV equipment
4.1 Lamps and ballasts
Every UV system starts with good lamp technology; both lamps and ballasts are critical. The lamp-ballast combination and the control principle determine system performance, running cost and stability. Because UV lamps must be submerged in water to disinfect, system operation also depends on the effectiveness and reliability of the automatic cleaning system. High-output low-pressure mercury lamps are generally used: they are the most economical in energy consumption while delivering maximum UV output. For the same power input, a good UV lamp emits four to five times the UV energy of an ordinary low-pressure mercury lamp. Fewer lamps are then needed, reducing design and operating costs, maintenance expenditure and installation cost.
Variable-output electronic ballasts should be selected: they adjust energy output to changes in flow and water quality, maximizing overall system reliability.
4.2 Automatic cleaning system
An automatic cleaning system that is easy to maintain and uses no chemicals is generally preferred. Specially designed cleaning rings operate continuously to prevent scaling on the quartz sleeves without interrupting disinfection, so maximum UV energy reaches the water. Cleaning frequency is adjusted automatically to wastewater characteristics. Even standby lamps remain clean and ready for service. Pneumatic, torque-free matrix operation cleans the lamps completely without any chemical cleaning agent.
4.3 Dose regulation, monitoring and control
The level of microbial inactivation depends on the UV dose received. UV intensity is determined mainly by three factors: effective UV output power, cleanliness of the quartz sleeve, and the transmittance of the wastewater. UV sensors (probes) installed in the lamp module operate automatically based on monitored UV intensity and wastewater flow, which determines exposure time.
To guarantee monitoring, sensors should be calibrated, self-cleaning and wavelength-selective, with stable operation and long service life. Real-time dose-controlled UV systems monitor and control the dose delivered to microorganisms continuously on the basis of UV intensity, automatically adjusting output to compensate for changes in water quality, lamp aging and lamp cleanliness.
5. Application outlook
Municipal wastewater treatment plants everywhere are upgrading, and UV sterilizers have broad application and market prospects. To protect rivers, lakes and coastal waters and ultimately human health, wastewater must be disinfected before discharge. UV disinfection for treatment plant effluent offers many advantages that other disinfectants cannot replace. Compared with liquid chlorine and chlorine dioxide, a UV sterilizer requires a slightly higher initial investment but has low annual operating cost, making it economically and technically feasible. In engineering applications, the UV system should be highly integrated and modular, with a simple structure and fully automatic operation, using long-life components to greatly reduce maintenance and management workload.