How to Select a UV Sterilizer for Secondary Water Supply

Secondary water supply is a critical part of urban water systems, and UV sterilizers are the mainstream disinfection equipment for it. Longkang provides professional UV sterilizer selection solutions tailored to the characteristics of secondary supply systems. This article explains how to select a UV sterilizer for secondary water supply.
1. Characteristics of secondary water supply systems
1.1 What is secondary water supply
Secondary water supply refers to supplying municipal water to users after it has been stored and pressurized by a building or facility. Common forms include elevated tanks, low-level tanks with pumps, non-negative-pressure systems, and variable-frequency systems. It is widely used in high-rise buildings, residential communities, hotels, hospitals, and schools.
1.2 Water quality risks
- Bacteria may grow in water tanks during storage
- Infrequent tank cleaning leads to deteriorating water quality
- Aging pipes cause secondary contamination
- Residual chlorine decays during storage
UV disinfection is an important measure to safeguard water quality.
1.3 Relevant standards
- GB 5749 — Standards for Drinking Water Quality
- GB 50015 — Code for Design of Building Water Supply and Drainage
- CJJ 140 — Technical Code for Secondary Water Supply Engineering
- Local secondary water supply regulations
These standards require secondary water supply facilities to be equipped with disinfection equipment.
2. Installation position of the UV sterilizer
2.1 At the tank outlet (recommended)
Installed on the outlet pipe of the living water tank. Water leaving the tank is disinfected before reaching users. Advantage: all stored water passes through disinfection. Drawback: bacteria can still grow inside the tank, so regular cleaning is required.
2.2 At the pump outlet
Installed at the outlet of the variable-frequency pump, disinfecting after pressurization. Advantage: stable pressure and flow. Drawback: only water pumped out is disinfected.
2.3 At the tank inlet (return-water disinfection)
Installed on the inlet pipe, disinfecting incoming water before it enters the tank. Advantage: prevents external contamination from entering the tank. Drawback: bacteria growing inside the tank are not treated.
2.4 Recommended scheme
- Primary: install the UV sterilizer at the tank outlet
- Auxiliary: clean the tank regularly (every six months)
- Optional: add UV at the tank inlet for double protection
3. Calculating treatment capacity
3.1 Design flow
Calculate based on the design instantaneous flow for building water supply, or the maximum hourly water consumption — not the daily average.
3.2 Reference maximum hourly consumption
| Building type | Water-use standard | Max. hourly consumption (est.) |
|---|---|---|
| 100 households | 200 L/person·day, 3.5 persons/household | approx. 8–12 m³/h |
| 200 households | 200 L/person·day | approx. 15–20 m³/h |
| 500 households | 200 L/person·day | approx. 30–50 m³/h |
| 100 hotel rooms | 300 L/bed·day | approx. 10–15 m³/h |
| 200 hotel rooms | 300 L/bed·day | approx. 20–30 m³/h |
| 100 hospital beds | 300 L/bed·day | approx. 10–15 m³/h |
| 500 students | 50 L/student·day | approx. 5–8 m³/h |
4. UV sterilizer selection
4.1 Dose requirement
- Drinking water: ≥40 mJ/cm²
- Recommended: 60 mJ/cm² (with reserve margin)
- Secondary supply water is generally of good quality (municipal tap water), so 40 mJ/cm² is sufficient
4.2 Equipment configuration
- Lamps: low-pressure UV lamps
- Chamber: 304 stainless steel
- Control: operation indicator + fault alarm + elapsed-time counter
- Optional: UV intensity monitor
4.3 Selection table
| Service scale | Capacity | Recommended model | Power | Lamps |
|---|---|---|---|---|
| Small residence (≤100 households) | 5–10 m³/h | LK-UV-10 | 160 W | 4 |
| Medium residence (100–300 households) | 10–20 m³/h | LK-UV-20 | 320 W | 4 |
| Large residence (300–500 households) | 20–30 m³/h | LK-UV-30 | 480 W | 6 |
| Very large residence (>500 households) | 30–50 m³/h | LK-UV-50 | 800 W | 10 |
| Small hotel (≤100 rooms) | 5–10 m³/h | LK-UV-10 | 160 W | 4 |
| Medium hotel (100–300 rooms) | 10–20 m³/h | LK-UV-20 | 320 W | 4 |
| Hospital (≤200 beds) | 10–20 m³/h | LK-UV-20 | 320 W | 4 |
| School (≤1,000 people) | 5–15 m³/h | LK-UV-10 | 160 W | 4 |
5. Special requirements for secondary supply
5.1 Hygiene and safety
- Chamber material: food-grade 304 stainless steel
- Sealing: food-grade fluororubber
- No secondary pollution
- Compliant with hygiene licensing requirements for water-contact products
5.2 Electrical safety
- Waterproof rating: IP65 (for humid pump rooms)
- Residual-current protection
- Reliable grounding
- Compliant with GB 4706 electrical safety standard
5.3 Operational reliability
- 24-hour continuous operation
- Fault alarm
- Long lamp life
- Easy maintenance
5.4 Energy saving
- High-efficiency electronic ballast
- Optional flow control (lamp off when no flow)
- Grouped lamp control
6. Installation notes
- Position: at the tank outlet or pump outlet for easy maintenance
- Bypass: provide a bypass valve so maintenance does not interrupt supply
- Valves: install valves before and after the unit
- Drain: provide a drain valve at the lowest point
- Space: reserve room for lamp replacement along the lamp axis
- Power: nearby power supply with waterproof socket
- Grounding: reliable earth connection
7. Acceptance requirements
- Model and specifications comply with the design
- Correct installation position and firm connections
- No leakage under water pressure test
- Normal operation when powered, indicators functioning
- UV intensity meets the standard
- Water testing: total bacterial count and total coliforms meet the standard
- Complete documentation: certificate of conformity, test report, hygiene permit
8. Longkang’s secondary supply solution
Longkang provides for secondary water supply:
- Professional selection calculation
- Food-grade 304 stainless steel chamber
- Low-pressure UV lamps with long service life
- Optional UV intensity monitoring
- Fault alarm and elapsed-time counter
- Hygiene permit for water-contact products
- Installation guidance and acceptance support
- Regular follow-up visits and maintenance service