Open-Channel UV Sterilizer Structure & Design

In large-scale treatment applications, the open channel is an effective and efficient way to convey water without expensive piping or pumps. An open-channel UV sterilizer is designed for applications where the treated fluid flows by gravity through an open channel. The system consists of a stainless steel frame — the “UV rack” — that supports the UV lamps vertically in the channel. Racks come in 12-lamp, 400 mm wide (16 in.) configurations or 24-lamp, 600 mm wide (24 in.) configurations.
Compared with horizontal UV equipment, vertical racks greatly reduce footprint and infrastructure requirements, and they fit particularly well into the typical chlorine contact chambers already present at wastewater treatment plants. Once installed, the vertical lamp rack rarely needs to be removed, because all lamps and quartz sleeves are accessible from the top of the rack, above the waterline.
Unlike the parallel flow of horizontal racks, vertical flow in a vertical rack produces excellent mixing that enhances UV flux. Lamps are also arranged in staggered arrays to further improve mixing. As a result, a failed lamp in a vertical system damages the average UV flux far less than in a horizontal rack, where water tends to flow laminarly along the length of the defective lamp.
1. UV rack hydraulic design
The hydraulic design of the rack and the placement of the lamps play an important role in UV treatment performance. The design uses a staggered lamp configuration that improves the uniformity of the UV intensity field. Strategically positioned flow breakers enhance fluid mixing to further increase the average UV flux (dose). Computational fluid dynamics (CFD) analysis of the hydraulics in the rack helps engineers design hydraulically efficient systems with minimal pressure drop across the rack and optimized flow velocities.
2. UV rack construction
The entire rack is made of highly corrosion-resistant 316L stainless steel, which surpasses 304 stainless steel in strength and in resistance to crevice and pitting corrosion. All stainless steel parts are welded by TIG or MIG techniques. The finished rack is electropolished, providing excellent corrosion resistance. All O-rings comply with FDA standards.
3. Open-channel UV performance
Open-channel UV racks handle flows from 150 m³/h to 350 m³/h (660 to 1,500 gpm), depending on water quality and the required UV flux rate (dose), with minimal head loss. The UV flux rate ranges from 30 to 300 mJ/cm² (30,000 to 300,000 μW·s/cm²), depending on flow and water quality. Any residual ozone is also quenched, protecting downstream equipment, users, and the environment.
4. Amalgam UV lamp technology
Open-channel UV treatment systems use amalgam lamp technology exclusively. Our high-performance amalgam lamps produce more than 400% more 254 nm UV light than conventional low-pressure UV lamps while maintaining lamp efficiency.
Amalgam lamps have several advantages over medium-pressure UV lamps. Any interruption of flow in a medium-pressure system causes overheating, because medium-pressure lamps operate at temperatures up to 900 °C while amalgam lamps operate at only about 100 °C. Quartz sleeve fouling is also more common in medium-pressure systems because of their higher UV density and lamp temperature, so sleeves must be cleaned more often. Lamp failure in an amalgam multi-lamp system is far less critical than in a medium-pressure system, where a single lamp failure can cut the UV flux level of a two-lamp unit by 50%. Medium-pressure lamps typically have a UVC efficiency of only 15%, whereas our amalgam lamps deliver at least 35%. The UV radiation field of our amalgam lamp systems is more uniform than that of medium-pressure systems because of the larger number of lamps in the flow. Considering all these factors, the overall system efficiency of an amalgam lamp system is far superior to that of a medium-pressure system.
When standard low-pressure lamp equipment performance is compared with our amalgam lamp equipment, one quickly realizes a reduction of 400% in the number of lamps, sleeves, and related hardware (both electrical and mechanical). This means significantly less equipment is needed to reach a given treatment level. Consequently, transportation cost, installation footprint and labor, infrastructure, and head loss are all substantially reduced, along with a fourfold reduction in maintenance time and labor associated with sleeve cleaning, lamp replacement, and general servicing.
Our amalgam lamps have an operating life of up to 16,000 hours, depending on operating conditions, the number of daily on/off cycles, and the duration of off periods. The life of our amalgam lamps is 3 to 4 times that of typical medium-pressure lamps. Our confidence in these lamps is such that we offer a 12,000-hour lamp life warranty, subject to certain terms and conditions.
5. Electronic ballasts
With energy costs a major concern today, the electrical efficiency of the whole UV system matters. Our high-efficiency electronic ballasts have a rated efficiency of 94% when paired with our amalgam lamps. They provide a constant drive level despite AC line voltage variations, keeping the lamp’s UVC output stable and maximizing lamp life. Ballasts are also energized in sequence, greatly reducing the UV system’s start-up inrush current — practically eliminating nuisance breaker trips.
6. Electrical control system
All our UV treatment systems integrate a programmable logic controller (PLC). It controls and monitors the operating status of the UV system and displays relevant parameters on a local backlit LCD. On a fault, the display also shows the fault location, and the operator is alerted by a visual indicator, an alarm relay, or an optional remote operator terminal (via an RS-485 multidrop link). The PLC monitors each UV lamp’s operating status and watches for equipment overheating; temperature monitoring is very useful for preventing damage to electrical equipment in high ambient temperature conditions.
The PLC cabinet provides filtered forced-air cooling to maximize the life of all electrical components. Air conditioning is available as an option when the installation environment exceeds 40 °C. MTBF data for FET semiconductor devices show that “every 10 °C reduction in junction temperature doubles the mean time between failures.”
7. Sensors
Sensors measure the relative UV intensity at the germicidal 254 nm wavelength inside the UV rack. The UV sensor output is processed by the PLC, which displays the relative intensity on the LCD in percent. The level is compared against setpoints established in the PLC to determine whether the relative UV intensity has fallen to or near the minimum needed for correct treatment. Appropriate visual alarm indicators are activated by the PLC to alert the operator of each condition. This function lets the operator notice when water quality is degrading or when the UV lamps are approaching the end of their life. The semiconductor devices used to detect 254 nm UV radiation are of highly advanced composition, degrading minimally under UV exposure over time, which helps ensure the sensor’s long-term accuracy.
By incorporating multiple strategically positioned sensors in the multi-lamp arrangement of the UV rack, a more accurate representation of the average UV field intensity inside the rack is obtained. This increases the effective UV sensing area and provides a more accurate representation of the average UV field intensity.
8. Maintenance of the UV system
Maintaining an open-channel UV sterilizer involves periodically cleaning the quartz sleeves and the electrical enclosure cooling fan filters, and periodically replacing lamps. Our proprietary 316 stainless steel quick-bayonet fittings give access to the UV lamps in under two seconds.
The quick-bayonet design makes the whole assembly virtually watertight: an O-ring integral with the bayonet fitting prevents splashed water from entering the quartz sleeve and damaging or short-circuiting the operating lamp. Additional seals inside the knurled compression nut prevent splashed water from entering through the lamp cable or the nut’s threads.
Depending on the application and water quality, quartz sleeves are cleaned periodically either with the optional manually operated sleeve wiper or with the optional automatic cleaning system, programmed to wipe the sleeves at an operator-set frequency.
Contact Longkang for sizing support and quotations.