Cleaning and Disinfection Procedure for Water Supply Tanks
This operating procedure summarizes the requirements for cleaning and disinfecting secondary water supply tanks, as practiced by Longkang in secondary supply projects. A tank self-cleaning sterilizer can automate routine disinfection, but periodic manual cleaning is still required.
1. Personnel requirements
All personnel engaged in tank cleaning and disinfection, including dedicated chemical preparation staff, must pass an annual medical examination by the health and epidemic prevention authority and hold a valid certificate, and must complete job training before starting work. Personnel found to have any of the five disqualifying diseases must be removed from the post immediately.
2. Clothing and tools
During cleaning and disinfection, workers must wear clean work clothes, rubber boots, and rubber gloves, and bring adequate lighting and dedicated cleaning tools (which must themselves be washed and disinfected beforehand) into the tank or pool.
3. Cleaning and disinfection procedure
- Issue an advance notice so residents can prepare.
- Close the inlet and outlet valves.
- Open the drain valve or start the submersible pump to lower the water level to about 30 cm, then close the valve or pump and block the outlet to keep dirt out.
- Workers enter the tank with dedicated tools and brushes and scrub from the roof to the floor, working from the inside outward; repair any damaged areas promptly.
- After scrubbing and inspection, open the drain valve or start the submersible pump to empty the dirty water, rinse with clean water, then close the valve or pump.
- Apply the prepared disinfectant solution evenly over the inner walls from top to bottom and from the inside outward, up to the manhole; then withdraw, and close the manhole cover.
- After 30 minutes, open the inlet valve; once the tank is full, drain it via the drain valve or submersible pump, then restore supply.
- On resuming supply, take samples for water quality testing by the health and epidemic prevention station; supply may continue only after the results pass.
4. Fittings and accessories
- Tank covers must be rainproof and sealed, made of corrosion-resistant, sturdy, lightweight material.
- Overflow openings must be fitted with mesh screens; repair any damage immediately.
- Manhole covers and access doors must be locked.
- Keep maintenance records for each tank.
5. Surroundings
The area around the tank must be kept clean, with no debris or garbage piled nearby. If the tank is buried, do not fertilize the ground above it, to prevent contaminated water from seeping into the tank.
6. Chemical handling
- Disinfectant storage and preparation must be the responsibility of a designated person, prepared centrally and stored in a dark, moisture-proof, sealed, cool place (the supernatant may be kept no longer than 48 hours).
- Cleaning and disinfection tools must be corrosion-resistant, washed and air-dried after use, and kept by a designated person.
7. Records
Keep one card per tank with detailed registration. By the end of November each year, report the number, location, and cleaning/disinfection status of all tanks to the competent authority and the district or county health and epidemic prevention station.
8. Precautions
- Observe labor protection and safety rules during cleaning.
- Prepare the disinfectant as a clear solution to prevent blockage of the sprayer; wear a mask when mixing chemicals.
9. Solution preparation
Stabilized chlorine dioxide: to disinfect a 1.0-ton tank, prepare 3 kg of solution at 200 ppm.
- Clean the inner walls of the tank.
- Measure 80 mL of the disinfectant stock solution, add 8 g of activator, shake or stir until dissolved; after 5 minutes, when it turns pale yellow, dilute into 8 kg of clean water for use.
- Spray the tank, applying all 8 kg of the diluted solution over the inner walls until wetted.
- Refill the tank 6 minutes after spraying. For bleach (calcium hypochlorite): mix 300 g of bleaching powder (or 150 g of refined bleaching powder) into a paste with a small amount of water, then add water to 10 kg, stir well, cover, let it settle, and use the supernatant. Dose at 200 mL of supernatant per square meter.
10. Recommendation for older tanks
For older tanks without disinfection equipment, Longkang recommends that property managers install a UV sterilizer at the tank outlet to provide continuous disinfection. Strict compliance with the requirements above ensures a smooth and safe tank cleaning and disinfection operation. Contact Longkang for sizing support and quotations.