Beijing UV Sterilizer Case: Controlling the Two Parasites at No.10 Waterworks

Case study: The Beijing No.10 Waterworks uses UV sterilizers to control the “two parasites”, Giardia and Cryptosporidium. This article reviews the regulatory background, the project configuration, the germicidal mechanism and the inactivation data behind that application.
1. Regulatory background: the “two parasites”
According to reports, the Beijing No.10 Waterworks uses UV sterilizers to control the “two parasites”. The term refers to Giardia and Cryptosporidium. Giardia parasitizes the human small intestine and gallbladder and can cause abdominal pain, diarrhoea and malabsorption; Cryptosporidium is a zoonotic protozoan disease whose main clinical manifestation is diarrhoea.
In North America, new drinking water standards set strict limits for Cryptosporidium, Giardia and disinfection by-products, and UV technology attracted serious attention. After studies confirmed UV as the most effective and feasible technology for controlling Cryptosporidium and Giardia, the United States Environmental Protection Agency (EPA) rapidly established application standards for UV technology in drinking water treatment. The second-stage Long-Term 2 Enhanced Surface Water Treatment Rule (LT2ESWTR), published in 2006, requires that drinking water treatment remove or inactivate 3 log of Giardia, 4 log of viruses and 4 log of Cryptosporidium.
Because chlorine disinfection has almost no effect on Cryptosporidium, LT2ESWTR requires existing plants to use filtration plus UV or ozone, while new plants must use filtration together with multi-stage combination disinfection.
2. UV adoption in North America
Larger UV-disinfecting water plants in North America include the Central Lake Water Plant in Chicago (180,000 m3/d), the Seattle water plant (680,000 m3/d) and the Victoria water plant in Vancouver (510,000 m3/d), as well as the Montreal water plant in Canada (3,000,000 m3/d). The Walkerton plant in Ontario, Canada, also adopted UV disinfection after the pathogenic-microorganism incident of 2000.
The UV sterilizer system being built for New York’s water supply has a treatment capacity of 8,360,000 m3/d and is currently the largest drinking water UV disinfection project in the world. Statistics show that in 2000 no large or medium-sized water plant in the United States had a UV sterilizer application; by 2006 the proportion of large and medium-sized plants using UV had risen to 10 percent. In recent years more UV projects have been built or put into service, and applying UV sterilizers to drinking water disinfection represents the development trend of disinfection technology.
3. Beijing No.10 Waterworks project profile
The Beijing No.10 Waterworks supplies 500,000 tonnes of water, mainly to Chaoyang, Tongzhou and Yizhuang. Its transmission pipeline has a diameter of 2.4 m and a length of 2.67 km. The line starts where the South-to-North Water Diversion eastern main canal meets Yaojiadian Road near the South Fifth Ring Road and runs east along the planned road alignment to the plant. Located in eastern Beijing, the plant covers about 180 mu.
Raw water will come mainly from the South-to-North Water Diversion, with Miyun Reservoir as a supplement, and the two sources can be switched. The plant uses a multi-barrier process of conventional treatment plus advanced treatment plus UV combined with chloramine disinfection. This effectively handles multiple source waters, keeps every effluent index in line with national drinking water standards and brings key indices to an advanced level.
4. The UV disinfection stage at the plant
Within the process flow of the Beijing No.10 Waterworks there is a UV disinfection room, a stage that is rare among the city’s existing plants. It uses UV sterilizers to inactivate Giardia and Cryptosporidium. Reports indicate that neither parasite has so far been found in Beijing’s local sources or in the South-to-North diversion source area, but both have appeared in parts of southern China. The UV sterilizer stage was added specifically to prevent the two parasites from entering Beijing with the diverted southern water, so that residents can drink with confidence.
5. How UV disinfection works
UV sterilizers are widely used and of high value in water treatment. Irradiation by UV light destroys and changes the structure of microbial DNA (deoxyribonucleic acid), causing bacteria to die immediately or to lose the ability to reproduce, thereby achieving sterilization. The band with true germicidal action is UVC, because C-band UV is readily absorbed by the DNA of living organisms, with radiation around 253.7 nm being the most effective.
UV disinfection is a purely physical method with advantages of simplicity and convenience, broad spectrum, no secondary pollution, easy management and easy automation. With the introduction of amalgam lamps and medium-pressure UV lamps, the application range of UV sterilizers continues to expand.
6. Germicidal efficiency against common microorganisms
Besides the “two parasites”, UV sterilizers can effectively kill many other bacteria and viruses. The table below shows the germicidal efficiency of UV technology against common bacteria and viruses at a UV radiation intensity of 30 W/cm2, with the required exposure time given in seconds.
| Category | Name | Time (s) | Category | Name | Time (s) |
|---|---|---|---|---|---|
| Bacteria | Bacillus anthracis | 0.30 | Bacteria | Mycobacterium tuberculosis | 0.41 |
| Corynebacterium diphtheriae | 0.25 | Vibrio cholerae | 0.64 | ||
| Clostridium tetani | 0.33 | Pseudomonas species | 0.37 | ||
| Clostridium botulinum | 0.80 | Salmonella species | 0.051 | ||
| Shigella dysenteriae | 0.15 | Enteric fever bacilli | 0.41 | ||
| Escherichia coli | 0.36 | Salmonella typhimurium | 0.53 | ||
| Viruses | Adenovirus | 0.10 | Viruses | Influenza virus | 0.23 |
| Bacteriophage | 0.20 | Poliovirus | 0.80 | ||
| Coxsackievirus | 0.08 | Rotavirus | 0.52 | ||
| Echovirus | 0.73 | Tobacco mosaic virus | 16 | ||
| Echovirus type I | 0.75 | Hepatitis B virus | 0.73 | ||
| Fungal spores | Aspergillus niger | 6.67 | Fungal spores | Soft spores | 0.30 |
| Aspergillus species | 0.73-8.80 | Penicillium species | 2.93-0.87 | ||
| Coprophilous fungi | 8.0 | Toxigenic Penicillium | 2.0-3.33 | ||
| Mucor species | 0.23-4.67 | Other Penicillium species | 0.87 | ||
| Algae | Blue-green algae | 10-40 | Algae | Paramecium species | 7.30 |
| Chlorella species | 0.93 | Green algae | 1.22 | ||
| Nematode eggs | 3.40 | Protozoa species | 4-6.7 | ||
| Fish diseases | Fungal disease | 1.60 | Fish diseases | Infectious pancreatic necrosis | 4.0 |
| White spot disease | 2.67 | Viral haemorrhagic disease | 1.6 |
7. Advantages and limitations
The main advantages of UV disinfection are fast germicidal action and no secondary pollution: Giardia and Cryptosporidium, which chlorine finds hard to kill, are readily killed by UV. There are also drawbacks. At insufficient power, photoreactivation can occur and bacteria and viruses may not be completely killed, so UV is generally used together with other processes. The No.10 Waterworks applies UV combined with chloramine disinfection, which both kills the “two parasites” and maintains a continuing germicidal effect during distribution.
For selection support and project-specific advice on UV disinfection applications, contact Longkang.