UV Sterilizers for Wastewater Treatment

As environmental protection has gained importance in China, products that cause no secondary pollution have developed rapidly, and UV disinfection equipment is one of them. Disinfection methods for water supply and drainage fall into two categories: chemical disinfection and physical disinfection. Chemical methods, however, often produce disinfection by-products. Residual chlorine in chlorine-based processes is toxic to fish and other organisms in receiving waters, and chemical methods such as chlorination have been found to generate by-products including trihalomethanes, carcinogenic and pathogenic factors and teratogenic substances. These findings have driven the search for a better disinfection method that produces no by-products and causes no secondary pollution, and interest has turned to the use of ultraviolet light for disinfection.
1. Development of UV disinfection technology
UV disinfection was first applied in the United States, where the US Environmental Protection Agency completed the first demonstration project for wastewater UV disinfection in 1970. The technology is now widely used in the United States and Canada. As a physical disinfection method, UV offers broad-spectrum germicidal action and no secondary pollution. After more than 30 years of development it has become a mature, reliable, efficient and environmentally sound disinfection technology, widely applied in many fields abroad. In China, understanding of the technology has been limited and its use in wastewater treatment has not been extensive. In recent years, with growing attention to wastewater disinfection and accumulated operating experience, UV disinfection is expected to be promoted. It is forecast that 80 percent of wastewater treatment plants with suitable conditions will adopt UV disinfection, making it the mainstream technology replacing conventional chemical disinfection.
2. Principles of ultraviolet light
Ultraviolet light is a form of electromagnetic wave. When electrons in an atom fall from a higher energy level to a lower one, the excess energy is released as an electromagnetic wave. The greater the energy of an electromagnetic wave, the higher its frequency and the shorter its wavelength. Visible light detectable by the human eye has a wavelength of 400–700 nm; to the eye, a 400 nm wave appears blue-violet and a 780 nm wave appears orange-red. Ultraviolet light refers to waves shorter than 400 nm. Because its spectrum lies beyond the violet region, it is called ultraviolet (UV). In general terms UV covers wavelengths from 100 nm to 400 nm and cannot be seen by the human eye.
UV in the 100–400 nm range is divided into UV-A, UV-B, UV-C and V-UV according to its effects on the human body and its functions.
UV-A covers 315–400 nm. UV-A stimulates melanin production in human skin and makes the skin darken.
UV-B covers 280–315 nm. UV-B can cause cancer and makes the skin wrinkle and age.
UV-C covers 200–280 nm, and the 254 nm band has germicidal and disinfecting effectiveness. UV-C between 240 nm and 270 nm can directly destroy the DNA and RNA of cells and viruses, causing microorganisms to die rapidly.
V-UV between 100 nm and 200 nm, specifically 185 nm, can generate ozone. Ozone in air or dissolved in water oxidises and destroys the cell walls of microorganisms, killing them immediately.
3. Germicidal mechanism of ultraviolet light
In all known forms of life on earth, DNA and RNA are the basis of reproduction and inheritance. Both DNA and RNA are built from four chemical units: A — adenine, T — thymine, C — cytosine and G — guanine.
When a cell reproduces, the long chains of DNA open. Each open chain seeks a complementary unit to bind with: A pairs with T, and each strand copies the partner strand that has just separated, restoring the complete DNA of the original cell and forming the basis of a new cell. UV at 240–270 nm can break the ability of DNA to produce proteins and to replicate. Once the DNA or RNA of a cell or virus is damaged, it loses both its ability to produce protein and its ability to reproduce. Because bacteria and viruses have short life cycles, those that can no longer reproduce die quickly.
4. Advantages and limitations of UV disinfection
Advantages
- UV disinfection requires no chemicals and produces no trihalomethane (THM) disinfection by-products.
- Germicidal action is fast and effective.
- There is no odour or noise, and the taste of the water is not affected.
- The process is easy to operate and manage, with low operating and maintenance costs.
Existing issues
- UV disinfection provides no residual disinfection capacity. After treated water leaves the reactor, some microorganisms injured by UV can repair damaged DNA through photoreactivation and regenerate. Further study of the principles and conditions of photoreactivation is needed to determine the minimum UV intensity, exposure time or dose that prevents it from occurring.
- Cleaning the outer wall of the quartz sleeve is key to operation and maintenance. As wastewater passes through the sterilizer, many inorganic impurities deposit and adhere to the sleeve. When the organic content of the wastewater is high, a fouling film forms more easily and microorganisms grow into a biofilm; both inhibit UV transmission and reduce disinfection effectiveness. Reasonable anti-fouling measures and cleaning devices must be selected according to water quality, and UV sterilizers with automatic cleaning should be developed.
- Domestic UV lamps currently follow the national industry standard for straight-tube quartz low-pressure mercury germicidal lamps, with a maximum lamp power of 4 W and an effective life generally of 1,000–3,000 hours. Imported low-pressure lamps can operate effectively for 8,000–12,000 hours and medium-pressure lamps for 5,000–6,000 hours. Using domestic lamps therefore raises maintenance costs, and developing long-life UV lamps or introducing advanced foreign lamp production technology is an urgent task.
- In current tenders for UV disinfection systems at Chinese wastewater plants, the colour of discharged wastewater is often deepened by large volumes of industrial effluent, while the UV transmittance parameter in tender documents still uses figures supplied from abroad. This creates a large gap from actual domestic wastewater conditions and leaves obstacles that are difficult to overcome if the equipment is to meet disinfection requirements in operation.
5. Longkang support for wastewater UV disinfection
Longkang supplies UV sterilizers for wastewater applications and provides selection support based on water quality, flow and discharge requirements. Contact Longkang for selection support and application advice on UV disinfection for your wastewater treatment project.