UV Sterilizer Selection for Ageing Water Supply Retrofits

Compact UV sterilizer installed at an ageing water tank outlet
Retrofitting an older water supply system with UV disinfection

Many older residential communities and office buildings have water supply systems built long ago without disinfection facilities, leaving water quality at risk. Adding a UV sterilizer is an effective way to retrofit an ageing water supply system. Longkang offers retrofit selection schemes tailored to the features of older systems. This article explains how to select a UV sterilizer for retrofitting an ageing water supply system.

1. Features of ageing water supply systems

1. Current condition

  • Built long ago, mostly before 2000
  • Tanks made of concrete or steel plate, prone to corrosion
  • Aged pipes that may be corroded
  • No disinfection facilities
  • Unstable water quality, with possible odour and turbidity

2. Retrofit challenges

  • Limited plant-room space
  • Non-standard pipe dimensions
  • Power supply capacity may be insufficient
  • Water cannot be shut off for long during construction
  • Limited budget

3. Retrofit objectives

  • Add disinfection facilities to safeguard water quality
  • Do not interrupt normal water supply
  • Keep the construction period short
  • Low investment and low operating cost
  • Easy maintenance

2. Choosing a retrofit scheme

1. Installation at the tank outlet, recommended

  • Install a UV sterilizer on the outlet pipe of the domestic water tank
  • Advantage: simple retrofit with no changes to the original system
  • Drawback: requires installation space at the tank outlet

2. Installation at the pump outlet

  • Install at the outlet of the variable-frequency pump
  • Advantage: stable pressure
  • Drawback: only water discharged by the pump is disinfected

3. Installation on the main inlet pipe

  • Install on the community’s main inlet pipe
  • Advantage: all incoming water is disinfected
  • Drawback: high flow, large equipment and high investment

4. Recommended scheme

  • First choice: install the UV sterilizer at the tank outlet
  • Multiple tanks: install one unit at each tank outlet
  • No tank, as in a non-negative-pressure system: install at the pump outlet

3. Determining treatment capacity

1. Based on existing pump flow

  • Check the nameplate flow of the existing pump
  • Select equipment by the rated pump flow
  • Multiple pumps: use the total flow of the maximum number of pumps running

2. Estimated from the number of households

  • Older communities generally use the actual number of households
  • Allow three to 3.5 persons per household
  • Allow 150–200 litres per person per day
  • Peak-hour variation coefficient of 2.5–3.0

3. Based on tank volume

  • Tank volume is generally 20–30 percent of daily water use
  • Peak-hour flow is approximately tank volume divided by two to three hours

4. Equipment selection for the retrofit

1. Equipment requirements

  • Compact size to suit limited space
  • Easy installation with flanged or threaded connections
  • 220 V power supply, since older plant rooms have limited capacity
  • Simple operation and easy maintenance
  • Reasonable price

2. Recommended models

Service scale Treatment capacity Recommended model Power Power supply
Small, up to 100 households 5–10 m³/h LK-UV-10 160 W 220 V
Medium, 100–300 households 10–20 m³/h LK-UV-20 320 W 220 V or 380 V
Large, 300–500 households 20–30 m³/h LK-UV-30 480 W 380 V

3. Configuration

  • Low-pressure UV lamps
  • 304 stainless steel chamber
  • Operation indicator and fault alarm
  • Lamp hour counter
  • Optional: UV intensity monitoring

5. Key construction points

1. Construction without shutting off water

  • Install a bypass pipe first
  • Put the bypass into service, then install the sterilizer
  • Switch over to the sterilizer after installation
  • Keep any water shutdown within two hours

2. Pipe connections

  • Existing pipes may be non-standard
  • Provide reducing connectors where needed
  • Use flanged or union connections
  • Ensure leak-free sealing

3. Power supply

  • Check the capacity of the existing power supply
  • A 220 V unit can generally use an existing socket
  • For a 380 V unit, confirm that a three-phase supply is available
  • Fit a residual-current protection switch

4. Space

  • Measure the dimensions of the installation position
  • Reserve room for lamp replacement
  • Reserve operating space
  • Choose a compact unit where space is insufficient

6. Acceptance after retrofit

  1. The equipment is firmly installed and connections are sealed
  2. No leakage under a water pressure test
  3. Normal operation when powered on
  4. UV intensity meets the standard
  5. Water testing: total bacterial count and total coliforms in the outlet meet the standard
  6. User feedback: water quality improved, with less odour and lower turbidity

7. Results of the retrofit

  1. Improved water quality: total bacterial count reduced by more than 99 percent
  2. Odour removed: odour generated during tank storage eliminated
  3. Cleaner pipes: less biofilm inside the pipes
  4. Safety assured: drinking water safety meets the standard
  5. Resident satisfaction: fewer complaints

8. Longkang retrofit service

Longkang provides the following for ageing water supply system retrofits:

  1. Free site survey to confirm installation conditions
  2. Recommend a retrofit scheme based on the existing system
  3. Compact equipment to suit limited space
  4. A construction scheme that avoids shutting off water
  5. Installation guidance or professional installation
  6. Support with water testing after the retrofit
  7. Competitive pricing and good value for money
  8. Long-term maintenance service

For UV sterilizer selection for an ageing water supply retrofit, contact Longkang.

UV disinfection, storage tank treatment, on-site hypochlorite (OSHG), chlorine dioxide and ozone systems for municipal, high-rise booster and industrial water.

Contact

Hotline +86 4008-780-280

Mobile / WhatsApp +86 130 1601 3265

R&D center, Guangzhou +86 20 28185170

Plant in Xianning, Hubei · R&D in Guangzhou, Guangdong