Standardized Tank Cleaning and Disinfection Procedure

Technician cleaning and disinfecting a secondary water supply tank
Standardized tank cleaning and disinfection workflow

Regular cleaning and disinfection is an important link in safeguarding water quality, and its quality is a key factor in water safety. To standardize tank cleaning and disinfection and ensure both the quality of the work and the safety of the water, the Standardized Operating Procedure for Cleaning and Disinfection of Secondary Water Supply Tanks has been established. A standardized operation flowchart accompanies the procedure.

1. Preliminary work

1.1 Prepare a cleaning plan

The operator of the secondary supply facility should draw up a cleaning and disinfection plan at the beginning of each year, with cleaning at least once every six months.

1.2 Commission a cleaning team

The operator should commission a specialist cleaning organization to carry out the work and sign a secondary supply facility cleaning and disinfection contract that sets out quality requirements and acceptance criteria.

1.3 Issue a notice

A water shutdown notice should be issued and posted as required, stating the time of the shutdown and telling users to make adequate storage preparations.

2. Cleaning during water shutdown

2.1 Prepare personnel, equipment and facilities

  1. Handover between the commissioning and contracted parties at the site should be completed properly, including a safety briefing.
  2. The on-site leader of the cleaning team should make clear the division of work and the specific requirements for all cleaning staff.

2.2 Close the tank inlet valve

  1. Close the main inlet valve and the connecting valves between tanks. Understanding the water-use pattern of the secondary supply area allows the inlet valve to be closed somewhat early, reducing the volume stored before cleaning and the water wasted by emptying the tank; a safety reserve should be kept to avoid shutting off water earlier than intended.
  2. Stop the pumps at the time stated in the shutdown notice so that supply to users ceases. Optimizing the compartmentalized management of tanks can keep the impact of cleaning and disinfection on users small or negligible.

2.3 Drain the stored water

Open the drain valve and discharge surplus water from the tank, leaving about 15 cm of tap water at the bottom.

2.4 Clean the tank according to the procedure

  1. Work strictly in accordance with confined-space operation requirements to ensure safety.
  2. The person in charge should brief cleaning and maintenance staff on the cleaning procedure, safety measures, technical requirements and precautions.
  3. Use a blower inserted through the manhole to ventilate the tank and keep air circulating inside.
  4. Install a 12 V or lower work light for illumination inside the tank.
  5. Using clean nylon brushes, dedicated mops and similar tools, scrub the top, surrounding walls, supports and bottom repeatedly in sequence to remove deposits from the walls and floor.
  6. Empty the water used for scrubbing from the tank bottom.
  7. Rinse the walls with clean water until the walls and bottom are completely clean.
  8. Disinfect according to the tank disinfection process. If bleaching powder is used, first mix 300 g of bleaching powder (or 150 g of bleaching essence powder) with a small amount of water to a paste, then add water to 10 kg, stir, cover and allow to settle; use the clear supernatant at a rate of 200 mL per square metre.
  9. After disinfection, rinse the top, walls and bottom three times with clean tap water.
  10. Slowly open the inlet valve and refill the tank.

3. Restoring water supply

3.1 Simple and formal water quality testing

  1. In the presence of the facility operator, the cleaning organization should use a portable water quality analyser on site to check residual chlorine and turbidity; water may be restored only once quality is acceptable.
  2. A qualified water testing agency should be commissioned to take samples for testing as required.

3.2 Prepare for draining and venting the pipework

  1. Check that air release valves in the pipework are working normally.
  2. Open outdoor fire hydrants in the supply area to drain and vent the system.

3.3 Confirm that equipment is in normal condition

Inspect the condition of facilities before water is admitted, focusing on equipment handled during the work and equipment prone to failure during shutdown and refilling.

3.4 Start the pumps

  1. Observe the operation of equipment and ensure that everything in the pump room runs normally.
  2. Any fault should be removed and repaired promptly.
  3. Close the hydrants that were opened once draining and venting are complete.

4. Cleanup

4.1 Site cleaning and tidying

  1. After the work is finished, count, tidy and put back all materials and equipment.
  2. Clear away work residues and keep the area around the tank clean and safe.

4.2 Check safety protection facilities

  1. Check that tank manholes are covered and locked.
  2. Check that the safety protection facilities for secondary supply have been returned to normal use.

5. Follow-up and feedback

5.1 Record information

  1. The operator should urge the cleaning organization to enter cleaning information into the secondary supply information system promptly.
  2. Any equipment fault occurring during cleaning and disinfection should be recorded together with the problem and its handling.

5.2 Track complaints

After cleaning and disinfection, the operator should follow user feedback once supply resumes and respond quickly to complaints. Complaints about water quality, pressure or lack of water should be analysed to identify causes and define corrective measures for future improvement.

Longkang provides equipment and selection support for secondary water supply cleaning and disinfection. Contact Longkang for selection support.

UV disinfection, storage tank treatment, on-site hypochlorite (OSHG), chlorine dioxide and ozone systems for municipal, high-rise booster and industrial water.

Contact

Hotline +86 4008-780-280

Mobile / WhatsApp +86 130 1601 3265

R&D center, Guangzhou +86 20 28185170

Plant in Xianning, Hubei · R&D in Guangzhou, Guangdong